생물안전밀폐시설에서 Multizone과 CFD 연동해석에 의한 실내기류 및 Influenza A 오염농도해석
DC Field | Value | Language |
---|---|---|
dc.contributor.author | 황지현 | - |
dc.contributor.author | 홍진관 | - |
dc.date.available | 2020-02-28T19:43:06Z | - |
dc.date.created | 2020-02-12 | - |
dc.date.issued | 2014 | - |
dc.identifier.issn | 1229-6422 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/gachon/handle/2020.sw.gachon/13240 | - |
dc.description.abstract | To maintain a negative pressure, the supply, exhaust airvolume are adjusted by setting volume damper and the infiltration through leakage area of the door between rooms in biosafety laboratory. Multizone simulation is useful way to predict room pressure, supply and exhaust air volume. But in a particular room, local change such as airflow and contaminants concentration distribution can not be evaluated unfortunately. Through this study, a coupled multizone and CFD simulation was performed, indoor air flow and local contaminants concentration distribution in a particular room of BSL lab are predicted. The results show that all zones of BSL lab are well ventilated by unidirectional flow without local stagnation. In addition, in case that unexpected biohazard is occured in BSL lab, multizone simulation results about the spread of pollutants along movement of the occupant also show that contaminants concentration is removing totally without the spread of the outside. In conclusion, a coupled multizone and CFD simulation can be applied to interpret differential pressure in room and local change of physical quantity in a particular room such as airflow and Influenza A contaminants concentration distribution. This simulation method is useful to enhance the reliability and accuracy of biosafety laboratory design. | - |
dc.language | 한국어 | - |
dc.language.iso | ko | - |
dc.publisher | 대한설비공학회 | - |
dc.relation.isPartOf | 설비공학 논문집 | - |
dc.title | 생물안전밀폐시설에서 Multizone과 CFD 연동해석에 의한 실내기류 및 Influenza A 오염농도해석 | - |
dc.title.alternative | Applications of a Coupled Multizone and CFD Simulation to Validate Airflow and Influenza A Contaminant Dispersion in Biosafety Laboratory | - |
dc.type | Article | - |
dc.type.rims | ART | - |
dc.description.journalClass | 2 | - |
dc.identifier.doi | 10.6110/KJACR.2014.26.12.588 | - |
dc.identifier.bibliographicCitation | 설비공학 논문집, v.26, no.12, pp.588 - 593 | - |
dc.identifier.kciid | ART001934902 | - |
dc.citation.endPage | 593 | - |
dc.citation.startPage | 588 | - |
dc.citation.title | 설비공학 논문집 | - |
dc.citation.volume | 26 | - |
dc.citation.number | 12 | - |
dc.contributor.affiliatedAuthor | 황지현 | - |
dc.contributor.affiliatedAuthor | 홍진관 | - |
dc.subject.keywordAuthor | Biosafety laboratory | - |
dc.subject.keywordAuthor | BSL lab.(생물안전 밀폐시설) | - |
dc.subject.keywordAuthor | Multizone smulation(멀티존 해석) | - |
dc.subject.keywordAuthor | CFD(전산유체역학) | - |
dc.subject.keywordAuthor | Coupled multizone and CFD simulation(멀티존_CFD 연동해석) | - |
dc.subject.keywordAuthor | Airflow(공기유동) | - |
dc.subject.keywordAuthor | Influenza A contaminants concentration(인플루엔자A 오염농도) | - |
dc.description.journalRegisteredClass | kci | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
1342, Seongnam-daero, Sujeong-gu, Seongnam-si, Gyeonggi-do, Republic of Korea(13120)031-750-5114
COPYRIGHT 2020 Gachon University All Rights Reserved.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.