Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

급배기 방식 개선에 따른 생물안전 밀폐시설의 Risk Assessment와 초기 건설비 저감에 대한 연구

Full metadata record
DC Field Value Language
dc.contributor.author황지현-
dc.contributor.author홍진관-
dc.contributor.author주영덕-
dc.date.available2020-02-29T02:42:27Z-
dc.date.created2020-02-12-
dc.date.issued2013-
dc.identifier.issn1229-6422-
dc.identifier.urihttps://scholarworks.bwise.kr/gachon/handle/2020.sw.gachon/15283-
dc.description.abstractIn general, entire supply air of the BSL3 laboratory should be vented to the outside for its biosafety and the air conditioning system should always be operating to maintain a room pressure difference. In this regard, annual energy consumption is approximately five or ten times greater than the magnitude of the office building. In addition, to adjust room pressure difference to the set value efficiently, the supply and exhaust duct system are installed in each room of the BSL3 lab. Thus, initial construction cost is extremely high. In this study, multizone simulation is performed to estimate maintaining the appropriate room pressure difference in the case of changing model A (each room supply and exhaust system) to model B (each zone supply and exhaust system) for verification of the BSL3 lab biosafety. Also, in the case of these two models, the multizone simulation for three kinds of biohazard scenario is performed as part of risk assessment. The analysis of initial construction cost of two models is conducted for comparison. According to the studies, initial construction cost of model B is less than about 22% of existing model A. Moreover, biosafety of the BSL3 lab is still maintaining in the case of the two models.-
dc.language한국어-
dc.language.isoko-
dc.publisher대한설비공학회-
dc.relation.isPartOf설비공학 논문집-
dc.title급배기 방식 개선에 따른 생물안전 밀폐시설의 Risk Assessment와 초기 건설비 저감에 대한 연구-
dc.title.alternativeA Study on the Risk Assessment and Reduction of Initial Construction Cost in a Biosafety Laboratory According to Improvement of Supply and Exhaust Method-
dc.typeArticle-
dc.type.rimsART-
dc.description.journalClass2-
dc.identifier.doi10.6110/KJACR.2013.25.10.534-
dc.identifier.bibliographicCitation설비공학 논문집, v.25, no.10, pp.534 - 539-
dc.identifier.kciidART001811999-
dc.citation.endPage539-
dc.citation.startPage534-
dc.citation.title설비공학 논문집-
dc.citation.volume25-
dc.citation.number10-
dc.contributor.affiliatedAuthor황지현-
dc.contributor.affiliatedAuthor홍진관-
dc.subject.keywordAuthorBiosafety laboratory-
dc.subject.keywordAuthorBSL3 lab(생물안전 밀폐시설)-
dc.subject.keywordAuthorBiohazard scenario(생물재해 시나리오)-
dc.subject.keywordAuthorSupply and exhaust duct system(급배기 시스템)-
dc.subject.keywordAuthorMultizone simulation(멀티죤 시뮬레이션)-
dc.subject.keywordAuthorRisk assessment(위해성평가)-
dc.subject.keywordAuthorInitial construction cost(초기 건설공사비)-
dc.description.journalRegisteredClasskci-
Files in This Item
There are no files associated with this item.
Appears in
Collections
공과대학 > 설비·소방공학과 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Hong, Jin Kwan photo

Hong, Jin Kwan
Engineering (Department of Building Equipment System&Fire Protection Engineering)
Read more

Altmetrics

Total Views & Downloads

BROWSE