공동주택 실내오염농도 평가에 의한 CO_2와 TVOC 센서기반 환기제어방법 특성 연구
DC Field | Value | Language |
---|---|---|
dc.contributor.author | 홍성민 | - |
dc.contributor.author | 윤동원 | - |
dc.date.available | 2020-02-29T08:46:21Z | - |
dc.date.created | 2020-02-12 | - |
dc.date.issued | 2012 | - |
dc.identifier.issn | 1226-9093 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/gachon/handle/2020.sw.gachon/17256 | - |
dc.description.abstract | The purpose of this study is to find the control strategies for ventilation and energy reduction with appropriate maintenance of indoor contaminant levels. According to a survey in other research, many mechanical ventilation systems are not often operated by residents, because residents tend to avoid powering their ventilation system in order to save utility cost. There isn't anything to inform sufficiently how to operating ventilation system for IAQ(Indoor Air Quality). And then, without any sufficient ventilation control strategies, it would be very difficult to improve IAQ by an occupant's manual control. If the ventilation unit is operating for 24 hour, the energy consumption would be dramatically increased. Therefore, the sensor based DCV control method is necessary for comfort and energy saving . It has been simulated both of CO_2 and TVOC sensors based DCV system for operating mechanical ventilation system. As a result of analysis, CO_2-DCV is not sufficient to maintain for comfort IAQ against TVOC from building materials and furnitures. Because CO_2 is generated irregularly by occupant’s schedules in individual room, but TVOC is emitted steadily from the finishing materials Therefore, CO_2-DCV couldn’t control the chemical contaminants like TVOC as below as the guideline. We must consider whether chemical contaminants are a proper target for control in an apartment house or not, because TVOC are more dangerous than CO_2.. | - |
dc.language | 한국어 | - |
dc.language.iso | ko | - |
dc.publisher | 대한건축학회 | - |
dc.relation.isPartOf | 대한건축학회논문집 계획계 | - |
dc.title | 공동주택 실내오염농도 평가에 의한 CO_2와 TVOC 센서기반 환기제어방법 특성 연구 | - |
dc.title.alternative | A Study on Characteristic of CO_2 and TVOC Sensor based Ventilation Control Strategies according to the Evaluation of Indoor Contaminant Level in an Apartment House | - |
dc.type | Article | - |
dc.type.rims | ART | - |
dc.description.journalClass | 2 | - |
dc.identifier.bibliographicCitation | 대한건축학회논문집 계획계, v.28, no.01, pp.303 - 310 | - |
dc.identifier.kciid | ART001630830 | - |
dc.citation.endPage | 310 | - |
dc.citation.startPage | 303 | - |
dc.citation.title | 대한건축학회논문집 계획계 | - |
dc.citation.volume | 28 | - |
dc.citation.number | 01 | - |
dc.contributor.affiliatedAuthor | 홍성민 | - |
dc.contributor.affiliatedAuthor | 윤동원 | - |
dc.subject.keywordAuthor | CO2-DCV | - |
dc.subject.keywordAuthor | TVOC-DCV | - |
dc.subject.keywordAuthor | Apartment House | - |
dc.subject.keywordAuthor | Ventilation Strategy | - |
dc.subject.keywordAuthor | CO2센서기반 환기제어 | - |
dc.subject.keywordAuthor | TVOC센서기반 환기제어 | - |
dc.subject.keywordAuthor | 공동주택 | - |
dc.subject.keywordAuthor | 환기방법 | - |
dc.description.journalRegisteredClass | kci | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
1342, Seongnam-daero, Sujeong-gu, Seongnam-si, Gyeonggi-do, Republic of Korea(13120)031-750-5114
COPYRIGHT 2020 Gachon University All Rights Reserved.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.