Utilization of Thermally Activated Building System with Horizontal Ground Heat Exchanger Considering the Weather Conditions
DC Field | Value | Language |
---|---|---|
dc.contributor.author | Chung, Woong June | - |
dc.contributor.author | Park, Sang Hoon | - |
dc.date.accessioned | 2021-12-27T07:40:04Z | - |
dc.date.available | 2021-12-27T07:40:04Z | - |
dc.date.created | 2021-12-05 | - |
dc.date.issued | 2021-12 | - |
dc.identifier.issn | 1996-1073 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/gachon/handle/2020.sw.gachon/82999 | - |
dc.description.abstract | The thermally activated building system (TABS) can reduce the peak load by integrating with the ground heat exchangers. When integrated, the cost of groundwork and stability of the ground temperature would counteract because the weather conditions would influence the ground temperature in shallow depth. However, previous studies on TABS assumed constant ground temperatures such as average outdoor air temperature. In this study, ground temperatures in different depths are simulated for their detailed investigations, and simulated results of ground temperature were applied to building energy simulations for observing the load-handled ratio (LHR), representing the peak load reduction by TABS evaluated in various weather conditions. Simulation results of ground temperatures from 1 m to 39 m depths show that the temperature stabilized at 2 m to 11 m depths depending on the characteristics of the outdoor air temperature. LHR increased as the ground depth increased because the ground temperature at shallow depths increased during peak hours. Ground depths of 8 m were found ideal for maintaining consistent LHR for all weather conditions. Detailed observation of ground temperature and its effect on LHR in various weather conditions can help system engineers design and operate the TABS with the ground system. © 2021 by the authors. Licensee MDPI, Basel, Switzerland. | - |
dc.language | 영어 | - |
dc.language.iso | en | - |
dc.publisher | MDPI | - |
dc.relation.isPartOf | Energies | - |
dc.title | Utilization of Thermally Activated Building System with Horizontal Ground Heat Exchanger Considering the Weather Conditions | - |
dc.type | Article | - |
dc.type.rims | ART | - |
dc.description.journalClass | 1 | - |
dc.identifier.wosid | 000734751900001 | - |
dc.identifier.doi | 10.3390/en14237927 | - |
dc.identifier.bibliographicCitation | Energies, v.14, no.23 | - |
dc.description.isOpenAccess | N | - |
dc.identifier.scopusid | 2-s2.0-85119966701 | - |
dc.citation.title | Energies | - |
dc.citation.volume | 14 | - |
dc.citation.number | 23 | - |
dc.contributor.affiliatedAuthor | Chung, Woong June | - |
dc.type.docType | Article | - |
dc.subject.keywordAuthor | EnergyPlus | - |
dc.subject.keywordAuthor | Ground heat exchanger | - |
dc.subject.keywordAuthor | KIVA | - |
dc.subject.keywordAuthor | Load-handled ratio | - |
dc.subject.keywordAuthor | Thermally activated building system | - |
dc.subject.keywordPlus | ADAPTIVE PREDICTIVE CONTROL | - |
dc.subject.keywordPlus | PUMP SYSTEMS | - |
dc.subject.keywordPlus | PERFORMANCE | - |
dc.subject.keywordPlus | TABS | - |
dc.subject.keywordPlus | GUIDELINES | - |
dc.subject.keywordPlus | SIMULATION | - |
dc.subject.keywordPlus | MASS | - |
dc.subject.keywordPlus | LOAD | - |
dc.relation.journalResearchArea | Energy & Fuels | - |
dc.relation.journalWebOfScienceCategory | Energy & Fuels | - |
dc.description.journalRegisteredClass | scie | - |
dc.description.journalRegisteredClass | scopus | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
1342, Seongnam-daero, Sujeong-gu, Seongnam-si, Gyeonggi-do, Republic of Korea(13120)031-750-5114
COPYRIGHT 2020 Gachon University All Rights Reserved.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.