Cited 0 time in
진공펌프 기체분리막을 이용한 제습증발냉각 외기전담시스템의 에너지 성능 평가
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | 천성용 | - |
| dc.contributor.author | 조혜진 | - |
| dc.contributor.author | 이수진 | - |
| dc.contributor.author | 정재원 | - |
| dc.date.accessioned | 2021-09-27T06:14:33Z | - |
| dc.date.available | 2021-09-27T06:14:33Z | - |
| dc.date.created | 2021-08-27 | - |
| dc.date.issued | 2021-06-25 | - |
| dc.identifier.uri | https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/132986 | - |
| dc.description.abstract | This study proposes a vacuum membrane dehumidifier and evaporative cooling-based dedicated outdoor air system to estimate the energy performance by a simulation study. The annual energy consumption of the proposed systems was compared with two Reference cases as conventional dedicated outdoor air systems; a DOAS with a desiccant wheel (Reference A) and a DOAS with a wet cooling coil (Reference B). The proposed DOAS deals with latent and sensible cooling separated by a vacuum-based membrane dehumidifier, which dries air with an isothermal process. The result shows that the annual average coefficient of performance of studied systems was 3.34 in the proposed system, 2.35 in Reference A, and 2.43 in Reference B. In summer, the average coefficient of performance of studied systems was 2.79 in the proposed system, 0.59 in Reference A, and 0.86 in Reference B, which is 4.73 and 3.24 higher than Reference A and Reference B. Because the proposed system is a decoupled sensible and latent cooling system using vacuum-based membrane dehumidifier and free cooling system (evaporative cooling), it is not required a thermally unwanted cooling and heating process; regeneration heat in Reference A and overcooling then reheating process in Reference B. Consequently, the proposed system reduced the total annual operation energy by 72.0% compared with Reference A and by 39.3% compared with Reference B. | - |
| dc.language | 한국어 | - |
| dc.language.iso | ko | - |
| dc.publisher | (사)대한설비공학회 | - |
| dc.title | 진공펌프 기체분리막을 이용한 제습증발냉각 외기전담시스템의 에너지 성능 평가 | - |
| dc.title.alternative | Energy performance of a vacuum membrane dehumidification and evaporative cooling based dedicated outdoor air system | - |
| dc.type | Conference | - |
| dc.contributor.affiliatedAuthor | 정재원 | - |
| dc.identifier.bibliographicCitation | 대한설비공학회 2021 하계학술발표대회, pp.607 - 610 | - |
| dc.relation.isPartOf | 대한설비공학회 2021 하계학술발표대회 | - |
| dc.relation.isPartOf | 대한설비공학회 2021 하계학술발표대회 논문집 | - |
| dc.citation.title | 대한설비공학회 2021 하계학술발표대회 | - |
| dc.citation.startPage | 607 | - |
| dc.citation.endPage | 610 | - |
| dc.citation.conferencePlace | KO | - |
| dc.citation.conferencePlace | 휘닉스 평창 | - |
| dc.citation.conferenceDate | 2021-06-22 | - |
| dc.type.rims | CONF | - |
| dc.description.journalClass | 2 | - |
| dc.identifier.url | https://www.auric.or.kr/User/Rdoc/DocRdoc.aspx?returnVal=RD_R&dn=407407#.YRxogt9t-Uk | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
222, Wangsimni-ro, Seongdong-gu, Seoul, 04763, Korea+82-2-2220-1366
COPYRIGHT © 2024 HANYANG UNIVERSITY.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.