Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

진공펌프 기체분리막을 이용한 제습증발냉각 외기전담시스템의 에너지 성능 평가

Full metadata record
DC Field Value Language
dc.contributor.author천성용-
dc.contributor.author조혜진-
dc.contributor.author이수진-
dc.contributor.author정재원-
dc.date.accessioned2021-09-27T06:14:33Z-
dc.date.available2021-09-27T06:14:33Z-
dc.date.created2021-08-27-
dc.date.issued2021-06-25-
dc.identifier.urihttps://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/132986-
dc.description.abstractThis study proposes a vacuum membrane dehumidifier and evaporative cooling-based dedicated outdoor air system to estimate the energy performance by a simulation study. The annual energy consumption of the proposed systems was compared with two Reference cases as conventional dedicated outdoor air systems; a DOAS with a desiccant wheel (Reference A) and a DOAS with a wet cooling coil (Reference B). The proposed DOAS deals with latent and sensible cooling separated by a vacuum-based membrane dehumidifier, which dries air with an isothermal process. The result shows that the annual average coefficient of performance of studied systems was 3.34 in the proposed system, 2.35 in Reference A, and 2.43 in Reference B. In summer, the average coefficient of performance of studied systems was 2.79 in the proposed system, 0.59 in Reference A, and 0.86 in Reference B, which is 4.73 and 3.24 higher than Reference A and Reference B. Because the proposed system is a decoupled sensible and latent cooling system using vacuum-based membrane dehumidifier and free cooling system (evaporative cooling), it is not required a thermally unwanted cooling and heating process; regeneration heat in Reference A and overcooling then reheating process in Reference B. Consequently, the proposed system reduced the total annual operation energy by 72.0% compared with Reference A and by 39.3% compared with Reference B.-
dc.language한국어-
dc.language.isoko-
dc.publisher(사)대한설비공학회-
dc.title진공펌프 기체분리막을 이용한 제습증발냉각 외기전담시스템의 에너지 성능 평가-
dc.title.alternativeEnergy performance of a vacuum membrane dehumidification and evaporative cooling based dedicated outdoor air system-
dc.typeConference-
dc.contributor.affiliatedAuthor정재원-
dc.identifier.bibliographicCitation대한설비공학회 2021 하계학술발표대회, pp.607 - 610-
dc.relation.isPartOf대한설비공학회 2021 하계학술발표대회-
dc.relation.isPartOf대한설비공학회 2021 하계학술발표대회 논문집-
dc.citation.title대한설비공학회 2021 하계학술발표대회-
dc.citation.startPage607-
dc.citation.endPage610-
dc.citation.conferencePlaceKO-
dc.citation.conferencePlace휘닉스 평창-
dc.citation.conferenceDate2021-06-22-
dc.type.rimsCONF-
dc.description.journalClass2-
dc.identifier.urlhttps://www.auric.or.kr/User/Rdoc/DocRdoc.aspx?returnVal=RD_R&dn=407407#.YRxogt9t-Uk-
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 2. Conference Papers

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE