Cited 0 time in
Experiment analysis and system design of PCM assisted thermoelectric radiant cooling panel
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | Kang, Yong Kwon | - |
| dc.contributor.author | Kim, Beom Jun | - |
| dc.contributor.author | Hwang, Yu-jin | - |
| dc.contributor.author | Ko, Jinyoung | - |
| dc.contributor.author | Jeong, Jae Weon | - |
| dc.date.accessioned | 2021-09-27T06:15:15Z | - |
| dc.date.available | 2021-09-27T06:15:15Z | - |
| dc.date.created | 2021-08-27 | - |
| dc.date.issued | 2020-12-03 | - |
| dc.identifier.uri | https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/133020 | - |
| dc.description.abstract | This study proposes a phase change material for use in radiant cooling panels integrated with thermoelectric modules (PCM–TERCP) and experimentally evaluates its performance characteristics during the cooling process in design conditions. The PCM–TERCP was proposed as a concept to reduce operating energy and costs by using phase change material for thermal energy storage, which is the disadvantage of the conventional thermoelectric radiant cooling panel. Moreover, the proposed system can achieve an off-peak operation. The empirical models predict the available cooling capacity and power consumption of the panel during the melting and solidification period of the PCM under the given conditions and predict the duration of each operation mode. The experiment results show the 58 W/m2, 54 W/m2 cooling capacity, and show 5 h, 2 h of the average cooling duration under the active and passive cooling process. Finally, using the proposed models as objective functions in this study suggests the optimum thickness of the PCM layer. The optimum results were determined to be 6–8 mm when minimizing electric power consumption. | - |
| dc.language | 영어 | - |
| dc.language.iso | en | - |
| dc.publisher | 한국생태환경건축학회 | - |
| dc.title | Experiment analysis and system design of PCM assisted thermoelectric radiant cooling panel | - |
| dc.type | Conference | - |
| dc.contributor.affiliatedAuthor | Jeong, Jae Weon | - |
| dc.identifier.bibliographicCitation | 2020년도 한국생태환경건축학회 추계국제학술발표대회, pp.175 - 181 | - |
| dc.relation.isPartOf | 2020년도 한국생태환경건축학회 추계국제학술발표대회 | - |
| dc.relation.isPartOf | 한국생태환경건축학회 2020년도 추계학술발표대회 논문집 제20권 제2호 | - |
| dc.citation.title | 2020년도 한국생태환경건축학회 추계국제학술발표대회 | - |
| dc.citation.startPage | 175 | - |
| dc.citation.endPage | 181 | - |
| dc.citation.conferencePlace | KO | - |
| dc.citation.conferencePlace | 한국과학기술회관 국제회의장, 온라인 Zoom | - |
| dc.citation.conferenceDate | 2020-12-03 | - |
| dc.type.rims | CONF | - |
| dc.description.journalClass | 1 | - |
| dc.identifier.url | https://www.dbpia.co.kr/journal/articleDetail?nodeId=NODE10523458 | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
222, Wangsimni-ro, Seongdong-gu, Seoul, 04763, Korea+82-2-2220-1366
COPYRIGHT © 2024 HANYANG UNIVERSITY.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.