Energy Benefit of Liquid Desiccant-Assisted Humidification in Buildings during Winter Operation
DC Field | Value | Language |
---|---|---|
dc.contributor.author | Lee, Soo-Jin | - |
dc.contributor.author | Lim, Hansol | - |
dc.contributor.author | Jeong, Jae-Weon | - |
dc.date.accessioned | 2022-07-07T00:32:37Z | - |
dc.date.available | 2022-07-07T00:32:37Z | - |
dc.date.created | 2021-07-14 | - |
dc.date.issued | 2021-03 | - |
dc.identifier.issn | 1996-1073 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/142223 | - |
dc.description.abstract | The objective of this study was to modify an existing liquid desiccant and indirect/direct evaporative cooling-assisted 100% outdoor air system (LD-IDECOAS) for humidification operation in winter. The energy benefit of the liquid desiccant-assisted humidification approach during the operation of LD-IDECOAS over the conventional method with a steam humidifier was evaluated through a detailed energy simulation. The humidification and enthalpy effectiveness values of the liquid desiccant humidification measured from laboratory tests were 0.41 and 0.49, respectively, which were applied to the energy simulation for the modified system. Both systems with the proposed and conventional humidification approaches were simulated using an engineering equation solver combined with a TRNSYS 18 energy simulation program. The results demonstrated that the modified LD-IDECOAS consumes less energy for humidification compared to the existing system with a steam humidifier. The proposed system also exhibited considerable heating energy-saving potential. Consequently, modified LD-IDECOAS consumed 42% less primary energy during winter operation after being modified for liquid desiccant-assisted humidification. | - |
dc.language | 영어 | - |
dc.language.iso | en | - |
dc.publisher | MDPI | - |
dc.title | Energy Benefit of Liquid Desiccant-Assisted Humidification in Buildings during Winter Operation | - |
dc.type | Article | - |
dc.contributor.affiliatedAuthor | Jeong, Jae-Weon | - |
dc.identifier.doi | 10.3390/en14051360 | - |
dc.identifier.scopusid | 2-s2.0-85106222365 | - |
dc.identifier.wosid | 000628205500001 | - |
dc.identifier.bibliographicCitation | ENERGIES, v.14, no.5, pp.1 - 14 | - |
dc.relation.isPartOf | ENERGIES | - |
dc.citation.title | ENERGIES | - |
dc.citation.volume | 14 | - |
dc.citation.number | 5 | - |
dc.citation.startPage | 1 | - |
dc.citation.endPage | 14 | - |
dc.type.rims | ART | - |
dc.type.docType | Article | - |
dc.description.journalClass | 1 | - |
dc.description.isOpenAccess | Y | - |
dc.description.journalRegisteredClass | scie | - |
dc.description.journalRegisteredClass | scopus | - |
dc.relation.journalResearchArea | Energy & Fuels | - |
dc.relation.journalWebOfScienceCategory | Energy & Fuels | - |
dc.subject.keywordPlus | Energy conservation | - |
dc.subject.keywordPlus | Evaporative cooling systems | - |
dc.subject.keywordPlus | Liquids | - |
dc.subject.keywordPlus | Conventional methods | - |
dc.subject.keywordPlus | Energy simulation | - |
dc.subject.keywordPlus | Energy simulation programs | - |
dc.subject.keywordPlus | Engineering equation solvers | - |
dc.subject.keywordPlus | Evaporative cooling | - |
dc.subject.keywordPlus | Outdoor-air systems | - |
dc.subject.keywordPlus | Primary energies | - |
dc.subject.keywordPlus | Winter operations | - |
dc.subject.keywordPlus | Driers (materials) | - |
dc.subject.keywordAuthor | liquid desiccant | - |
dc.subject.keywordAuthor | humidification | - |
dc.subject.keywordAuthor | heat pump | - |
dc.subject.keywordAuthor | steam humidifier | - |
dc.identifier.url | https://www.mdpi.com/1996-1073/14/5/1360 | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
222, Wangsimni-ro, Seongdong-gu, Seoul, 04763, Korea+82-2-2220-1365
COPYRIGHT © 2021 HANYANG UNIVERSITY.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.