진공펌프 기반 기체분리막 제습장치의 제습 성능에 대한 실험적 연구
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | 천성용 | - |
| dc.contributor.author | 조혜진 | - |
| dc.contributor.author | 강용권 | - |
| dc.contributor.author | 조수영 | - |
| dc.contributor.author | 이수진 | - |
| dc.contributor.author | 정재원 | - |
| dc.date.accessioned | 2022-07-07T11:11:27Z | - |
| dc.date.available | 2022-07-07T11:11:27Z | - |
| dc.date.created | 2021-05-14 | - |
| dc.date.issued | 2020-11 | - |
| dc.identifier.uri | https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/144357 | - |
| dc.description.abstract | This study aims to estimate the performance of vacuum-based membrane dehumidifier and investigate the system characteristics by experimental study. The performance of the system was evaluated by inlet/outlet humidity ratio difference with 4 independent parameters: air temperature, humidity ratio, airflow rate, and membrane type. The parametric study was designed for 27 experiment sets based on 3 levels of independent parameters. The results showed that the inlet/outlet humidity ratio difference of each membrane type was 4.5 g/kg to 18.9 g/kg (Type 1), 5.5 g/kg to 19.1 g/kg (Type 2), and 6.2 to 20.2 g/kg (Type 3). Evaluating from 3 levels of the parametric study, the air temperature and humidity ratio have a positive collection with inlet/outlet humidity ratio difference, and the air flowrate has a negative collection with inlet/outlet humidity ratio difference. The dehumidification performance of the membrane type where the surface area increase is applied was improved by about 21%. In future research, we intend to establish the operation mode of the system and develop for system design, based on the experimental results. | - |
| dc.language | 한국어 | - |
| dc.language.iso | ko | - |
| dc.publisher | 대한설비공학회 | - |
| dc.title | 진공펌프 기반 기체분리막 제습장치의 제습 성능에 대한 실험적 연구 | - |
| dc.title.alternative | Experimental Study for dehumidification performance of vacuum-based membrane dehumidifier | - |
| dc.type | Article | - |
| dc.contributor.affiliatedAuthor | 정재원 | - |
| dc.identifier.bibliographicCitation | 대한설비공학회 2020 동계학술발표대회 논문집, pp.136 - 139 | - |
| dc.relation.isPartOf | 대한설비공학회 2020 동계학술발표대회 논문집 | - |
| dc.citation.title | 대한설비공학회 2020 동계학술발표대회 논문집 | - |
| dc.citation.startPage | 136 | - |
| dc.citation.endPage | 139 | - |
| dc.type.rims | ART | - |
| dc.type.docType | Proceeding | - |
| dc.description.journalClass | 2 | - |
| dc.description.isOpenAccess | N | - |
| dc.description.journalRegisteredClass | other | - |
| dc.subject.keywordAuthor | Vacuum-based membrane dehumidifier | - |
| dc.subject.keywordAuthor | Dehumidification performance | - |
| dc.subject.keywordAuthor | Parametric study | - |
| dc.subject.keywordAuthor | 기체분리막 제습장치 | - |
| dc.subject.keywordAuthor | 제습 성능 | - |
| dc.subject.keywordAuthor | 파라메트릭 스터디 | - |
| dc.identifier.url | https://www.auric.or.kr/User/Rdoc/DocRdoc.aspx?returnVal=RD_R&dn=402599#.YRxxzt9t-Uk | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
222, Wangsimni-ro, Seongdong-gu, Seoul, 04763, Korea+82-2-2220-1366
COPYRIGHT © 2024 HANYANG UNIVERSITY.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.