Cited 0 time in
증발냉각 응축기 기반 공기열원 히트펌프의 에너지 절감 효과 분석
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | 김범준 | - |
| dc.contributor.author | 조수영 | - |
| dc.contributor.author | 강용권 | - |
| dc.contributor.author | 정재원 | - |
| dc.date.accessioned | 2022-07-08T00:20:47Z | - |
| dc.date.available | 2022-07-08T00:20:47Z | - |
| dc.date.created | 2021-05-14 | - |
| dc.date.issued | 2020-06 | - |
| dc.identifier.uri | https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/145493 | - |
| dc.description.abstract | The main purpose of this study is to investigate the energy saving potential analysis of a spryed-condenser assisted air-source heat pump used in an office building during summer season. A direct evaporative cooler was installed on the inlet side of the condenser to enhance the heat exchange performance. The hot ambient air was introduced to the direct evaporative cooler and cooled nearly wet bulb temperature by evaporative cooling effect. The cooled air treated by direct evaporative cooler was introduced to the condenser. A energy recovery ventilation was installed for ventilation of the occupants, and all of the sensible and latent load of the office building is removed by the proposed and existing heat pump system. The simulation was conducted by Engineering Equation Solver (EES) and TRNSYS 18 for model building thermal load simulation. The result was showed that proposed heat pump system is saved 26.4% of primary energy consumption than existing heat pump system in summer. This can be solve the problem of maximum power demand and overheating in summer with simple installation. | - |
| dc.language | 한국어 | - |
| dc.language.iso | ko | - |
| dc.publisher | 대한설비공학회 | - |
| dc.title | 증발냉각 응축기 기반 공기열원 히트펌프의 에너지 절감 효과 분석 | - |
| dc.title.alternative | Energy saving potential of sprayed-condenser assisted air-source heat pump | - |
| dc.type | Article | - |
| dc.contributor.affiliatedAuthor | 정재원 | - |
| dc.identifier.bibliographicCitation | 대한설비공학회 2020 하계학술발표대회 논문집, pp.162 - 165 | - |
| dc.relation.isPartOf | 대한설비공학회 2020 하계학술발표대회 논문집 | - |
| dc.citation.title | 대한설비공학회 2020 하계학술발표대회 논문집 | - |
| dc.citation.startPage | 162 | - |
| dc.citation.endPage | 165 | - |
| dc.type.rims | ART | - |
| dc.type.docType | Proceeding | - |
| dc.description.journalClass | 2 | - |
| dc.description.isOpenAccess | N | - |
| dc.description.journalRegisteredClass | other | - |
| dc.subject.keywordAuthor | Evaporative cooling | - |
| dc.subject.keywordAuthor | Condenser | - |
| dc.subject.keywordAuthor | Heat pump | - |
| dc.subject.keywordAuthor | Building energy saving | - |
| dc.subject.keywordAuthor | 증발냉각 | - |
| dc.subject.keywordAuthor | 응축기 | - |
| dc.subject.keywordAuthor | 히트펌프 | - |
| dc.subject.keywordAuthor | 건물에너지 절감 | - |
| dc.identifier.url | https://www.auric.or.kr/User/Rdoc/DocRdoc.aspx?returnVal=RD_R&dn=398901#.YRxsW99t-Uk | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
222, Wangsimni-ro, Seongdong-gu, Seoul, 04763, Korea+82-2-2220-1366
COPYRIGHT © 2024 HANYANG UNIVERSITY.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.