Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Heat pump를 적용한 액체식 제습 시스템의 겨울철 가습 운전에 대한 실험적 연구

Full metadata record
DC Field Value Language
dc.contributor.author임한솔-
dc.contributor.author이수진-
dc.contributor.author동혜원-
dc.contributor.author조혜진-
dc.contributor.author정재원-
dc.date.accessioned2022-07-09T00:29:54Z-
dc.date.available2022-07-09T00:29:54Z-
dc.date.created2021-05-14-
dc.date.issued2019-11-
dc.identifier.urihttps://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/146760-
dc.description.abstractThe performance of regenerator in heat pump integrated liquid desiccant (LD) system was investigated for the operation in winter. The performance parameters for regenerator were the regeneration effectiveness and enthalpy exchange effectiveness. There were five independent parameters of inlet air temperature, inlet air humidity ratio, inlet solution temperature, concentration of solution and liquid-to-gas ratio. The experimental model was constructed using an adiabatic cross flow regenerator with lithium chloride solution. Based on 2k and 3k factorial design method, total 48 experiment sets were designed to develop prediction models for two performance parameters. The results showed that the solution temperature and liquit-to-gas ratio have significant effects on the regeneration effectiveness and enthalpy exchange effectiveness of regenerator. In addition, the amount of humidification was ranged from 3.23 g/㎏a to 51.18 g/㎏a, therefore it was enough for humidification system in winter.-
dc.language한국어-
dc.language.isoko-
dc.publisher(사)대한설비공학회-
dc.titleHeat pump를 적용한 액체식 제습 시스템의 겨울철 가습 운전에 대한 실험적 연구-
dc.title.alternativeExperimental study for humidification operation of heat pump integrated liquid desiccant system in winter-
dc.typeArticle-
dc.contributor.affiliatedAuthor정재원-
dc.identifier.bibliographicCitation대한설비공학회 2019 동계학술발표대회 논문집, pp.261 - 264-
dc.relation.isPartOf대한설비공학회 2019 동계학술발표대회 논문집-
dc.citation.title대한설비공학회 2019 동계학술발표대회 논문집-
dc.citation.startPage261-
dc.citation.endPage264-
dc.type.rimsART-
dc.type.docTypeProceeding-
dc.description.journalClass2-
dc.description.isOpenAccessN-
dc.description.journalRegisteredClassother-
dc.subject.keywordAuthorLiquid desiccant system-
dc.subject.keywordAuthorRegenerator-
dc.subject.keywordAuthorHumidification-
dc.subject.keywordAuthorLithium chloride-
dc.subject.keywordAuthor액체식 제습 시스템-
dc.subject.keywordAuthor재생기-
dc.subject.keywordAuthor가습-
dc.subject.keywordAuthor염화 리튬-
dc.identifier.urlhttps://www.dbpia.co.kr/journal/articleDetail?nodeId=NODE09317635-
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE