Cited 0 time in
유기 랭킨 사이클이 적용된 제습증발냉각기반 공동주택 중앙환기시스템의 에너지 성능 분석
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | 동혜원 | - |
| dc.contributor.author | 조혜진 | - |
| dc.contributor.author | 유소 | - |
| dc.contributor.author | 정재원 | - |
| dc.date.accessioned | 2022-07-09T13:57:21Z | - |
| dc.date.available | 2022-07-09T13:57:21Z | - |
| dc.date.created | 2021-05-14 | - |
| dc.date.issued | 2019-06 | - |
| dc.identifier.uri | https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/147528 | - |
| dc.description.abstract | The purpose of this research is to analyze the energy performance of the organic Rankine cycle (ORC) applied to a centralized liquid desiccant and evaporative cooling-assisted ventilation system in an apartment building. As a small combined heat and power application in apartment buildings, the ORC produces heat and power consumed by the proposed system and building. A conventional decentralized energy recovery ventilator (ERV) served by the existing power grid was chosen as a reference system. The ORC integrated with liquid desiccant and evaporative cooling-assisted ventilation system can offer energy savings by recovering heat from the ORC condenser compared to conventional ERVs. As a result, the proposed system could provide supply air with better condition and reduce the parallel system energy consumption. Consequently, the proposed system saved 27% annual primary energy with better system COP compared that of the ERV when the power produced from the ORC was applied for the common electricity of the building. | - |
| dc.language | 한국어 | - |
| dc.language.iso | ko | - |
| dc.publisher | (사)대한설비공학회 | - |
| dc.title | 유기 랭킨 사이클이 적용된 제습증발냉각기반 공동주택 중앙환기시스템의 에너지 성능 분석 | - |
| dc.title.alternative | Energy Saving Assessment of a Centralized Liquid Desiccant and Evaporative Cooling-assisted Ventilation System with an Organic Rankine Cycle in an Apartment Building | - |
| dc.type | Article | - |
| dc.contributor.affiliatedAuthor | 정재원 | - |
| dc.identifier.bibliographicCitation | 대한설비공학회 2019 하계학술발표대회 논문집, pp.728 - 731 | - |
| dc.relation.isPartOf | 대한설비공학회 2019 하계학술발표대회 논문집 | - |
| dc.citation.title | 대한설비공학회 2019 하계학술발표대회 논문집 | - |
| dc.citation.startPage | 728 | - |
| dc.citation.endPage | 731 | - |
| dc.type.rims | ART | - |
| dc.type.docType | Proceeding | - |
| dc.description.journalClass | 2 | - |
| dc.description.isOpenAccess | N | - |
| dc.description.journalRegisteredClass | other | - |
| dc.subject.keywordAuthor | Organic Rankine cycle | - |
| dc.subject.keywordAuthor | Liquid desiccant | - |
| dc.subject.keywordAuthor | Evaporative cooling | - |
| dc.subject.keywordAuthor | Ventilation system | - |
| dc.subject.keywordAuthor | Energy recovery ventilator | - |
| dc.subject.keywordAuthor | 유기 랭킨 사이클 | - |
| dc.subject.keywordAuthor | 액체식 제습 시스템 | - |
| dc.subject.keywordAuthor | 증발냉각 | - |
| dc.subject.keywordAuthor | 환기시스템 | - |
| dc.subject.keywordAuthor | 전열교환환기장치 | - |
| dc.identifier.url | https://www.dbpia.co.kr/journal/articleDetail?nodeId=NODE09293878 | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
222, Wangsimni-ro, Seongdong-gu, Seoul, 04763, Korea+82-2-2220-1366
COPYRIGHT © 2024 HANYANG UNIVERSITY.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.