Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Evaluation of UR-UVGI System for Sterilization Effect on Microorganism Contamination in Negative Pressure Isolation Wardopen access

Authors
Bang, Jong-IlPark, JeongyeonChoi, AnseopJeong, Jae-WeonKim, Jin YongSung, Minki
Issue Date
Sep-2018
Publisher
MDPI
Keywords
negative pressure isolation ward; upper room-ultraviolet germicidal irradiation; airborne microorganisms; numerical simulation
Citation
Sustainability, v.10, no.9, pp.1 - 19
Indexed
SCIE
SSCI
SCOPUS
Journal Title
Sustainability
Volume
10
Number
9
Start Page
1
End Page
19
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/149398
DOI
10.3390/su10093192
ISSN
2071-1050
Abstract
A negative pressure isolation ward prevents the outflow of airborne microorganisms from inside the ward, minimizing the spread of airborne contamination causing respiratory infection. In response to recent outbreaks of severe acute respiratory syndrome (SARS) and Middle East respiratory syndrome (MERS), Korea has increased the number of these facilities. However, airborne contaminants that flow into the ward from adjacent areas may cause secondary harm to patients. In this study, the sterilization effect of upper-room ultraviolet germicidal irradiation (UR-UVGI) on microorganisms generated within the negative pressure isolation ward and those flowing inward from adjacent areas was evaluated through field experiments and computational fluid dynamics (CFD) analysis, to assess the potential of this approach as a supplementary measure to control such microorganisms. The sterilization effect was found to be not high because of high-level ventilation. CFD analysis under various conditions shows that the sterilization effect for indoor-generated microorganisms varies with the level of UV radiation, the source locations of the indoor-generated microorganisms, air supplies and exhausts, the UVGI system, and the airflow formed under the specified conditions. Our results show that when the UVGI system is installed in the upper part of the ward entrance, contaminated air from adjacent area is strongly sterilized.
Files in This Item
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE