Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Experimental verification of indirect evaporative cooling assisted internally cooled liquid desiccant dehumidifieropen access

Authors
Park, Joon YoungJeong, Jae Weon
Issue Date
Jul-2018
Publisher
Purdue University
Citation
2018 Purdue Conference Proceedings, pp.1 - 10
Indexed
OTHER
Journal Title
2018 Purdue Conference Proceedings
Start Page
1
End Page
10
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/149661
Abstract
The main objective of this study is to estimate the system performance of an evaporative cooling assisted internally cooled liquid desiccant dehumidifier (ICLD). The feasibility of an evaporative cooling assisted ICLD is analyzed using an environmental climate chamber test for a variation in the working airflow on the evaporative cooling channel. In the process air channel of the ICLD, the air stream was maintained at a constant mass flow rate when the working air steam was changed to modulate the increase in airflow ratio from 0.25 to 1.0. The ICLD performance was measured under a constant temperature and humidity to simulate hot and humid outdoor air conditions. To evaluate its performance, the cooling capacity, wet-bulb effectiveness, coefficient of performance, and volumetric mass transfer coefficient of the ICLD were evaluated based on the measured data. As the results indicate, the 0.5 ratio of airflow between the working and process air stream showed a higher performance in terms of dehumidification and sensible cooling than a different airflow ratio.
Files in This Item
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE