Preventing condensation and frosting in an energy recovery ventilator using a preheat coil
DC Field | Value | Language |
---|---|---|
dc.contributor.author | Kim, Won-Jun | - |
dc.contributor.author | Li, Shiying | - |
dc.contributor.author | Jo, Min-suk | - |
dc.contributor.author | Choi, Eun-ji | - |
dc.contributor.author | Jeong, Jae Weon | - |
dc.date.accessioned | 2022-07-13T11:28:40Z | - |
dc.date.available | 2022-07-13T11:28:40Z | - |
dc.date.created | 2021-05-14 | - |
dc.date.issued | 2017-09 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/151580 | - |
dc.description.abstract | One of the problems presented by energy recovery ventilators (ERV) is the condensation/frosting problem that occurs during winter time. In order to prevent this problem, preheating outdoor air is the most common method used nowadays. The aim of this research is to evaluate preheat coil capacities according to different indoor/outdoor inlet air conditions (temperatures and humidities) and sensible/latent effectiveness of ERV (εS, εL). Considering all these factors, formulas for calculating a frost threshold temperature (TFrost)are suggested, Tfrost being the minimum inlet outdoor temperature at which condensation/frosting occurs under specific conditions. As a result, a control strategy for operating preheat coils for preventing condensation/frosting problems in ERVs is presented. For an ERV operating under outdoor inlet air conditions of -15 ˚C and 70% indoor inlet air conditions of 22˚C and 50% humidity, and sensible effectiveness is 80%, latent effectiveness is 70%, the capacity needed for the preheat coil is 227 W. In addition, preheat coil capacities were calculated for the operation of an ERV in a few cities of AIVC countries. | - |
dc.language | 영어 | - |
dc.language.iso | en | - |
dc.publisher | AIVC | - |
dc.title | Preventing condensation and frosting in an energy recovery ventilator using a preheat coil | - |
dc.type | Article | - |
dc.contributor.affiliatedAuthor | Jeong, Jae Weon | - |
dc.identifier.bibliographicCitation | Proceedings of 2017 AIVC Conference, pp.97 - 105 | - |
dc.relation.isPartOf | Proceedings of 2017 AIVC Conference | - |
dc.citation.title | Proceedings of 2017 AIVC Conference | - |
dc.citation.startPage | 97 | - |
dc.citation.endPage | 105 | - |
dc.type.rims | ART | - |
dc.type.docType | Proceeding | - |
dc.description.journalClass | 1 | - |
dc.description.isOpenAccess | N | - |
dc.description.journalRegisteredClass | other | - |
dc.identifier.url | https://www.aivc.org/resource/preventing-condensation-and-frosting-energy-recovery-ventilator-using-preheat-coil | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
222, Wangsimni-ro, Seongdong-gu, Seoul, 04763, Korea+82-2-2220-1365
COPYRIGHT © 2021 HANYANG UNIVERSITY.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.