대향류형 액체식 제습시스템의 제습 성능 예측을 위한 수치적 및 경험적 모델 비교분석

Full metadata record
DC Field Value Language
dc.contributor.author조혜진-
dc.contributor.author박준영-
dc.contributor.author천성용-
dc.contributor.author조민석-
dc.contributor.author정재원-
dc.date.accessioned2022-07-14T01:48:41Z-
dc.date.available2022-07-14T01:48:41Z-
dc.date.created2021-05-14-
dc.date.issued2017-06-
dc.identifier.issn1229-6422-
dc.identifier.urihttps://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/152088-
dc.description.abstractThis paper aims to propose the numerical model of counter flow type liquid desiccant (LD) system and to compare the dehumidification effectiveness between the numerical model and empirical model to verify the accuracy of the predicting performance of the proposed numerical model. A heat and mass transfer correlations using NTU as an input parameter are employed to solve this system model equations for predicting dehumidifications effectiveness. The simulation results were compared with the results from the empirical model presented in existing literatures. The 24 groups are chosen based on the air properties conditions for the liquid desiccant performance test and the valid parameter range of the empirical model. For the 24 groups of both predicted and experimental results, the overall discrepancy is within 20%, which proves that the calculated results by the model accord well with the experimental findings.-
dc.language한국어-
dc.language.isoko-
dc.publisher대한설비공학회-
dc.title대향류형 액체식 제습시스템의 제습 성능 예측을 위한 수치적 및 경험적 모델 비교분석-
dc.title.alternativeComparison of a numerical and empirical model for predicting the dehumidification effectiveness of a counter flow type liquid desiccant system-
dc.typeArticle-
dc.contributor.affiliatedAuthor정재원-
dc.identifier.doi10.6110/KJACR.2016.28.6.001-
dc.identifier.bibliographicCitation대한설비공학회대한설비공학회 학술발표대회논문집, v.28, no.11, pp.541 - 544-
dc.relation.isPartOf대한설비공학회대한설비공학회 학술발표대회논문집-
dc.citation.title대한설비공학회대한설비공학회 학술발표대회논문집-
dc.citation.volume28-
dc.citation.number11-
dc.citation.startPage541-
dc.citation.endPage544-
dc.type.rimsART-
dc.type.docTypeProceeding-
dc.description.journalClass2-
dc.description.isOpenAccessN-
dc.description.journalRegisteredClassother-
dc.subject.keywordAuthorliquid desiccant system-
dc.subject.keywordAuthorcounter flow type-
dc.subject.keywordAuthordehumidification effectiveness model-
dc.subject.keywordAuthornumerical model-
dc.subject.keywordAuthorempirical model-
dc.subject.keywordAuthor액체식 제습 시스템-
dc.subject.keywordAuthor대향류형-
dc.subject.keywordAuthor제습 효율 예측 모델-
dc.subject.keywordAuthor수치 모델-
dc.subject.keywordAuthor실험모델-
dc.identifier.urlhttps://www.dbpia.co.kr/journal/articleDetail?nodeId=NODE07224234-
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE