수중건물에 적용된 액체식 제습증발냉각기반 전외기 공조시스템의 연간 에너지 소비 및 성능 분석

Full metadata record
DC Field Value Language
dc.contributor.author조민석-
dc.contributor.author박준영-
dc.contributor.author신장훈-
dc.contributor.author최병남-
dc.contributor.author정재원-
dc.date.accessioned2022-07-14T23:53:59Z-
dc.date.available2022-07-14T23:53:59Z-
dc.date.issued2016-12-
dc.identifier.issn1976-6483-
dc.identifier.issn2586-0666-
dc.identifier.urihttps://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/153369-
dc.description.abstractThe purpose of this paper is to analyze the operating energy consumption and performance of a liquid desiccant and evaporative cooling-assisted 100% outdoor air system (LD-IDECOAS) applied in an underwater building. Due to distinct features in surrounding environments of the underwater building from an above ground building, the thermal loads of the underwater building showed difference which affected the energy consumptions of the buildings accordingly. To estimate the energy consumption of the LD-IDECOAS, the office buildings located above the ground and underwater were assumed to be 625㎡ in size and have accommodations for 32 people. The thermal loads of the designed buildings were calculated using TRNSYS 17. According to the required thermal load of the modeling space, the energy simulation was conducted to evaluate the annual operating energy of the LD-IDECOAS using a commercial engineering equation solver (EES). As a result, the LD-IDECOAS in the underwater building showed 48% reduction in the energy consumption compared to that in the above ground building. Furthermore, the system performance was increased and the system capacity was reduced.-
dc.format.extent6-
dc.language한국어-
dc.language.isoKOR-
dc.publisher한국건축친환경설비학회-
dc.title수중건물에 적용된 액체식 제습증발냉각기반 전외기 공조시스템의 연간 에너지 소비 및 성능 분석-
dc.title.alternativeAnnual Energy Consumption and Performance Analysis of a Liquid Desiccant and Evaporative Cooling-assisted 100% Outdoor Air System in an Underwater Building-
dc.typeArticle-
dc.publisher.location대한민국-
dc.identifier.bibliographicCitation한국건축친환경설비학회 논문집, v.10, no.6, pp 456 - 461-
dc.citation.title한국건축친환경설비학회 논문집-
dc.citation.volume10-
dc.citation.number6-
dc.citation.startPage456-
dc.citation.endPage461-
dc.identifier.kciidART002177714-
dc.description.isOpenAccessN-
dc.description.journalRegisteredClasskci-
dc.subject.keywordAuthorLiquid desiccant system-
dc.subject.keywordAuthorUnderwater building-
dc.subject.keywordAuthorOutdoor air system-
dc.subject.keywordAuthorEvaporative cooling system-
dc.subject.keywordAuthorBuilding energy-
dc.subject.keywordAuthor액체식 제습시스템-
dc.subject.keywordAuthor수중건물-
dc.subject.keywordAuthor전외기 공조시스템-
dc.subject.keywordAuthor증발냉각 시스템-
dc.subject.keywordAuthor건물에너지-
dc.identifier.urlhttps://www.dbpia.co.kr/journal/articleDetail?nodeId=NODE07111378-
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE