Cited 0 time in
제습 증발냉각 기반 전 외기 공조시스템의 환기 성능 평가
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | 윤동섭 | - |
| dc.contributor.author | 이성준 | - |
| dc.contributor.author | 박준영 | - |
| dc.contributor.author | 정재원 | - |
| dc.date.accessioned | 2022-07-15T20:27:23Z | - |
| dc.date.available | 2022-07-15T20:27:23Z | - |
| dc.date.created | 2021-05-14 | - |
| dc.date.issued | 2015-10 | - |
| dc.identifier.issn | 2287-5786 | - |
| dc.identifier.uri | https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/156055 | - |
| dc.description.abstract | In this study, ventilation performance of liquid desiccant in an evaporative-cooling assisted 100% outdoor air system was evaluated. Carbon-dioxide gas was used as a tracer gas to evaluate the ventilation performance. Air change rate (ACR) was considered as a ventilation efficiency index. CO₂ gas was injected in to test room of 81 m³ and concentration decay was measured when ventilating room with LD-IDECOAS and VAV system. Supply air flow rate of two system is set to 1500 CMH and 1200 CMH of return air was used in VAV system. Conquently, it was found that the LD-IDECOAS has better ventilation performance than VAV system. | - |
| dc.language | 한국어 | - |
| dc.language.iso | ko | - |
| dc.publisher | 대한건축학회 | - |
| dc.title | 제습 증발냉각 기반 전 외기 공조시스템의 환기 성능 평가 | - |
| dc.title.alternative | Ventilation performance evaluation of liquid desiccant in an evaporative-cooling assisted 100% outdoor air system | - |
| dc.type | Article | - |
| dc.contributor.affiliatedAuthor | 정재원 | - |
| dc.identifier.bibliographicCitation | 대한건축학회 창립70주년기념대회 및 추계학술발표대회논문집, v.35, no.2, pp.281 - 282 | - |
| dc.relation.isPartOf | 대한건축학회 창립70주년기념대회 및 추계학술발표대회논문집 | - |
| dc.citation.title | 대한건축학회 창립70주년기념대회 및 추계학술발표대회논문집 | - |
| dc.citation.volume | 35 | - |
| dc.citation.number | 2 | - |
| dc.citation.startPage | 281 | - |
| dc.citation.endPage | 282 | - |
| dc.type.rims | ART | - |
| dc.type.docType | Proceeding | - |
| dc.description.journalClass | 2 | - |
| dc.description.isOpenAccess | N | - |
| dc.description.journalRegisteredClass | other | - |
| dc.subject.keywordAuthor | 환기 | - |
| dc.subject.keywordAuthor | 추적기체법 | - |
| dc.subject.keywordAuthor | 전 외기 공조시스템 | - |
| dc.subject.keywordAuthor | 시간 당 환기 횟수 | - |
| dc.subject.keywordAuthor | Ventilation | - |
| dc.subject.keywordAuthor | tracer gas technique | - |
| dc.subject.keywordAuthor | 100% outdoor air system | - |
| dc.subject.keywordAuthor | air change rate | - |
| dc.identifier.url | https://www.dbpia.co.kr/journal/articleDetail?nodeId=NODE06524799 | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
222, Wangsimni-ro, Seongdong-gu, Seoul, 04763, Korea+82-2-2220-1366
COPYRIGHT © 2024 HANYANG UNIVERSITY.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.