친환경 가스 중 전극과 고체절연체의 불량접촉에 관한 절연진단연구open accessStudy on Insulation Diagnosis of Poor Contact between Electrode and Solid Insulator in Eco-Gas
- Other Titles
- Study on Insulation Diagnosis of Poor Contact between Electrode and Solid Insulator in Eco-Gas
- Authors
- 임동영; 최은혁; 배성우; 최상태; 이광식; 최병주
- Issue Date
- Oct-2015
- Publisher
- 한국조명.전기설비학회
- Keywords
- Insulation Diagnosis; Partial Discharge; Poor Contact; Radiated Electromagnetic Waves
- Citation
- 조명.전기설비학회논문지, v.29, no.10, pp.97 - 103
- Indexed
- KCI
- Journal Title
- 조명.전기설비학회논문지
- Volume
- 29
- Number
- 10
- Start Page
- 97
- End Page
- 103
- URI
- https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/156118
- DOI
- 10.5207/JIEIE.2015.29.10.097
- ISSN
- 1229-4691
- Abstract
- This paper presents the characteristics of partial discharge and radiated electromagnetic waves in the existence of a poor contact for the insulation diagnosis of eco-friendly power equipment. AC surface discharge experiment was conducted to simulate the poor contact between a hive voltage electrode (anode) and a solid insulator in N2/O2 mixture gas under a non-uniform field. The partial discharge voltage to be measured at 0.3MPa increased with the increase of the poor contact gap and was saturated with the gap. In addition to the partial discharge characteristics, it was verified that the defect of the poor contact can be diagnosed using the radiated electromagnetic waves due to the partial discharge, which measured by a biconical EMC antenna and a spectrum analyzer.
- Files in This Item
-
- Appears in
Collections - 서울 공과대학 > 서울 전기공학전공 > 1. Journal Articles
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.