Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

고분자 전해질 연료전지(PEMFC)가 적용된 제습증발냉각 전외기 공조시스템의 연간 1차 에너지 절감량 분석Analysis of primary energy saving for PEM fuel cell with a liquid desiccant and evaporative cooling-assisted all outdoor air system

Other Titles
Analysis of primary energy saving for PEM fuel cell with a liquid desiccant and evaporative cooling-assisted all outdoor air system
Authors
조수영정재원
Issue Date
Aug-2015
Publisher
한국건축친환경설비학회
Keywords
Polymer electrolyte membrane fuel cell; CHP(combined heat and power); evaporative cooler; liquid desiccant; predicted model; primary energy; 고분자전해질 연료전지; 열병합발전; 제습 증발냉각; 액체식 제습; 성능 예측 모델; 1차 에너지
Citation
한국건축친환경설비학회 논문집, v.9, no.4, pp.292 - 297
Indexed
KCI
Journal Title
한국건축친환경설비학회 논문집
Volume
9
Number
4
Start Page
292
End Page
297
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/156604
ISSN
1976-6483
Abstract
The main purpose of this paper is to estimate primary energy saving of polymer electrolyte membrane fuel cell (PEM fuel cell) for a liquid desiccant indirect and direct evaporative cooling assisted 100% outdoor air system (LD-IDECOAS). Also, we have suggested the PEM fuel cell performance predicted model by experiments. The fuel cell system provides the electric power and thermal energy by combining hydrogen and oxygen simultaneously. If waste heat is used, the total energy efficiency of fuel cell is up to 85%. The PEM fuel cell is suitable as a system for supplying power and heat sources to LD-IDECOAS. Using the measured load profile of the pilot system, the required electric capacity of the fuel cell system was designed at 10 kW. To suggest the performance predicted model of fuel cell, several test were conducted in the facility of pilot system. The predicted model was used to calculate the annual primary energy saving of a fuel cell. In this research, the performance of the previous systems using conventional gas-fired boiler and purchased electricity are compared with that of the proposed system to evaluate energy saving potential.
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE