Energy saving potential of various air-side economizers in a modular data center
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | Ham, Sang-Woo | - |
| dc.contributor.author | Kim, Min-Hwi | - |
| dc.contributor.author | Choi, Byung-Nam | - |
| dc.contributor.author | Jeong, Jae-Weon | - |
| dc.date.accessioned | 2022-07-16T01:03:47Z | - |
| dc.date.available | 2022-07-16T01:03:47Z | - |
| dc.date.issued | 2015-01 | - |
| dc.identifier.issn | 0306-2619 | - |
| dc.identifier.issn | 1872-9118 | - |
| dc.identifier.uri | https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/158177 | - |
| dc.description.abstract | With the recent development of the IT technology, the demand for data centers has significantly increased, and modular data centers have attracted considerable attention because of their excellent stability, scalability, and economic feasibility. This research quantitatively analyzed the applicability of various air-side economizers and their energy-saving potential in modular data centers. A detailed cooling load estimation process was established for modular data centers, and annual cooling energy simulations were carried out using various air-side economizers. The various air-side economizers yielded cooling coil load savings of 76-99% in comparison to conventional cooling systems in data centers, and the total cooling energy savings of the economizers ranged from 47.5% to 67.2%. Indirect air-side economizers with high-effectiveness heat exchangers were found to yield significant energy saving (63.6%) and have simple system configurations. | - |
| dc.format.extent | 18 | - |
| dc.language | 영어 | - |
| dc.language.iso | ENG | - |
| dc.publisher | Pergamon Press Ltd. | - |
| dc.title | Energy saving potential of various air-side economizers in a modular data center | - |
| dc.type | Article | - |
| dc.publisher.location | 영국 | - |
| dc.identifier.doi | 10.1016/j.apenergy.2014.10.066 | - |
| dc.identifier.scopusid | 2-s2.0-84920070229 | - |
| dc.identifier.wosid | 000347582700023 | - |
| dc.identifier.bibliographicCitation | Applied Energy, v.138, pp 258 - 275 | - |
| dc.citation.title | Applied Energy | - |
| dc.citation.volume | 138 | - |
| dc.citation.startPage | 258 | - |
| dc.citation.endPage | 275 | - |
| dc.type.docType | Article | - |
| dc.description.isOpenAccess | N | - |
| dc.description.journalRegisteredClass | sci | - |
| dc.description.journalRegisteredClass | scie | - |
| dc.description.journalRegisteredClass | scopus | - |
| dc.relation.journalResearchArea | Energy & Fuels | - |
| dc.relation.journalResearchArea | Engineering | - |
| dc.relation.journalWebOfScienceCategory | Energy & Fuels | - |
| dc.relation.journalWebOfScienceCategory | Engineering, Chemical | - |
| dc.subject.keywordPlus | SYSTEMS | - |
| dc.subject.keywordAuthor | Modular data center | - |
| dc.subject.keywordAuthor | Cooling system | - |
| dc.subject.keywordAuthor | Air-side economizer | - |
| dc.subject.keywordAuthor | Evaporative cooling | - |
| dc.subject.keywordAuthor | Energy savings | - |
| dc.identifier.url | https://www.sciencedirect.com/science/article/abs/pii/S0306261914011167?via%3Dihub | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
222, Wangsimni-ro, Seongdong-gu, Seoul, 04763, Korea+82-2-2220-1366
COPYRIGHT © 2024 HANYANG UNIVERSITY.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.