Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Inverse Model Toolkit을 이용한 리모델링 건축물의 에너지 성능평가 사례

Full metadata record
DC Field Value Language
dc.contributor.author권경우-
dc.contributor.author이석주-
dc.contributor.author박준석-
dc.date.accessioned2022-07-16T03:36:38Z-
dc.date.available2022-07-16T03:36:38Z-
dc.date.created2021-05-13-
dc.date.issued2014-08-
dc.identifier.issn1229-6422-
dc.identifier.urihttps://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/159362-
dc.description.abstractSeveral models and methods have been developed to verify the improvement of energy performance in retrofit buildings. The verification is important to confirm the effectiveness of new technologies or retrofits. Inverse model toolkit proposed by ASHRAE evaluates the changes of the energy performance of retrofit buildings by using actual energy consumption data. In this study, the inverse model toolkit was used to analyze heating and cooling energy performance of an office building. Analyzed coefficients of correlation of actual energy consumption with estimated energy consumption was above 0.92 and well fitted. It was confirmed that energy consumption of natural gas decreased by 43.4% and also that electricity decreased by 13.8%, after the retrofit of the case building. For the energy usage, cooling energy was increased by 7.4%, heating energy was decreased by 42.3%, hot water and cooking were increased by 3.4%, lighting and electronics were decreased by 19.3%, and the total energy was decreased by 18.9%.-
dc.language한국어-
dc.language.isoko-
dc.publisher대한설비공학회-
dc.titleInverse Model Toolkit을 이용한 리모델링 건축물의 에너지 성능평가 사례-
dc.title.alternativeA Case Study on Energy Performance Analysis of Retrofitted Building Using Inverse Model Toolkit-
dc.typeArticle-
dc.contributor.affiliatedAuthor박준석-
dc.identifier.doi10.6110/KJACR.2014.26.5.394-
dc.identifier.bibliographicCitation설비공학 논문집, v.26, no.8, pp.394 - 400-
dc.relation.isPartOf설비공학 논문집-
dc.citation.title설비공학 논문집-
dc.citation.volume26-
dc.citation.number8-
dc.citation.startPage394-
dc.citation.endPage400-
dc.type.rimsART-
dc.identifier.kciidART001900079-
dc.description.journalClass2-
dc.description.isOpenAccessN-
dc.description.journalRegisteredClasskci-
dc.subject.keywordAuthorEnergy Consumption(에너지 소비)-
dc.subject.keywordAuthorEnergy Performance(에너지 성능)-
dc.subject.keywordAuthorRetrofit(리모델링)-
dc.subject.keywordAuthorCase Study(사례분석)-
dc.subject.keywordAuthorInverse Model Toolkit-
dc.identifier.urlhttps://www.auric.or.kr/User/Rdoc/DocRdoc.aspx?returnVal=RD_R&dn=321198#.YhLvWuhByUk-
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Park, Jun Seok photo

Park, Jun Seok
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE