Cited 0 time in
공조기를 이용한 가압테스트를 통한 외피 기밀도 실측
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | 한슬기 | - |
| dc.contributor.author | 조홍재 | - |
| dc.contributor.author | 정재원 | - |
| dc.date.accessioned | 2022-07-16T13:10:51Z | - |
| dc.date.available | 2022-07-16T13:10:51Z | - |
| dc.date.created | 2021-05-13 | - |
| dc.date.issued | 2012-10 | - |
| dc.identifier.uri | https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/164440 | - |
| dc.description.abstract | This research is a case study performing the air-andler fan pressurization test in a real building. The test has been performed follwing an exiting test method(i.e. CGSB 149.15-96 Standrard). The test building is a 5-story office with a square (32.4m × 32.4m) footprint built in 2001 at Dae-jeon. The test building gas four air-handling units, but the unit located at the basement was out of order. Consequently, the 3 air-handling units installed at the 1st floor and 5th floor were used to pressurize the building. To measure the whole building envelope air leakage, the SA airflow rates in each air handler, operated at the 100% outdoor air mode with closed return and exhaust air dampers, were monitored together with the building pressure. This paper provides some practical information acquired in the field measurement of envelope leakage using the established air-handler fan pressurization test method. | - |
| dc.language | 한국어 | - |
| dc.language.iso | ko | - |
| dc.publisher | 한국건축친환경설비학회 | - |
| dc.title | 공조기를 이용한 가압테스트를 통한 외피 기밀도 실측 | - |
| dc.title.alternative | Building Envelope leakage measurement using the air-handler fan pressurization approach | - |
| dc.type | Article | - |
| dc.contributor.affiliatedAuthor | 정재원 | - |
| dc.identifier.bibliographicCitation | 한국건축친환경설비학회 2012년도 추계학술발표대회, pp.109 - 112 | - |
| dc.relation.isPartOf | 한국건축친환경설비학회 2012년도 추계학술발표대회 | - |
| dc.citation.title | 한국건축친환경설비학회 2012년도 추계학술발표대회 | - |
| dc.citation.startPage | 109 | - |
| dc.citation.endPage | 112 | - |
| dc.type.rims | ART | - |
| dc.type.docType | Proceeding | - |
| dc.description.journalClass | 3 | - |
| dc.description.isOpenAccess | N | - |
| dc.description.journalRegisteredClass | other | - |
| dc.subject.keywordAuthor | 공조기를 이용한 가압테스트 | - |
| dc.subject.keywordAuthor | 건물 기밀도 | - |
| dc.subject.keywordAuthor | 팬 가압 테스트 | - |
| dc.subject.keywordAuthor | 건물 침기량 | - |
| dc.subject.keywordAuthor | AHU pressurization test | - |
| dc.subject.keywordAuthor | Air-tightness | - |
| dc.subject.keywordAuthor | Air leakage test | - |
| dc.subject.keywordAuthor | Buildling Envelope | - |
| dc.identifier.url | https://www.auric.or.kr/User/Rdoc/DocRdoc.aspx?returnVal=RD_R&dn=290687#.YhQ6cuhBxPY | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
222, Wangsimni-ro, Seongdong-gu, Seoul, 04763, Korea+82-2-2220-1366
COPYRIGHT © 2024 HANYANG UNIVERSITY.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.