Cited 0 time in
Experimental Study on Dehumidification Performance of a Vacuum-Based Membrane Dehumidifier
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | Cheon, Seong-Yong | - |
| dc.contributor.author | Lee, Soo-Jin | - |
| dc.contributor.author | Lin, Li-Hua | - |
| dc.contributor.author | Jeong, Jae-Weon | - |
| dc.date.accessioned | 2023-09-04T07:04:23Z | - |
| dc.date.available | 2023-09-04T07:04:23Z | - |
| dc.date.issued | 2021-06 | - |
| dc.identifier.issn | 0001-2505 | - |
| dc.identifier.uri | https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/189636 | - |
| dc.description.abstract | Dehumidification performance in HVAC systems for decoupled air conditioning becomes more important as the airtightness and insulation in buildings increases. The vacuum-based membrane dehumidifier (VMD), which creates a partial vapor gradient between membrane layers using a vacuum pump, has high energy saving potential when employed for isothermal dehumidification. Most previous studies have focused on evaluating the dehumidification and energy performance of vacuum-based membrane dehumidifiers with theoretical or numerical analysis. Experimental studies on vacuum-based membrane dehumidifiers with various air conditions are very rare for HVAC systems. In this study, we fabricated a prototype of a vacuum-based membrane dehumidifier made of a hollow fiber membrane and evaluated its dehumidification performance in terms of various air conditions (i.e., inlet air temperature, inlet air humidity ratio, inlet air velocity, and vacuum pump pressure). The experimental results showed that the main parameters affecting the dehumidification performance were the vacuum pump pressure and the inlet air velocity. Furthermore, a regression model based on a statistical analysis was derived using the Design-Expert program. The prediction model showed an R2value of 95.4% compared with the experimental data. | - |
| dc.format.extent | 9 | - |
| dc.language | 영어 | - |
| dc.language.iso | ENG | - |
| dc.title | Experimental Study on Dehumidification Performance of a Vacuum-Based Membrane Dehumidifier | - |
| dc.type | Article | - |
| dc.identifier.scopusid | 2-s2.0-85167413487 | - |
| dc.identifier.bibliographicCitation | ASHRAE Transactions, v.127, pp 457 - 465 | - |
| dc.citation.title | ASHRAE Transactions | - |
| dc.citation.volume | 127 | - |
| dc.citation.startPage | 457 | - |
| dc.citation.endPage | 465 | - |
| dc.type.docType | Conference paper | - |
| dc.description.isOpenAccess | N | - |
| dc.description.journalRegisteredClass | scopus | - |
| dc.subject.keywordPlus | Air | - |
| dc.subject.keywordPlus | Humidity control | - |
| dc.subject.keywordPlus | HVAC | - |
| dc.subject.keywordPlus | Regression analysis | - |
| dc.subject.keywordPlus | Vacuum pumps | - |
| dc.subject.keywordPlus | Air velocities | - |
| dc.subject.keywordPlus | Airtightness | - |
| dc.subject.keywordPlus | Condition | - |
| dc.subject.keywordPlus | Dehumidification performance | - |
| dc.subject.keywordPlus | Energy savings potential | - |
| dc.subject.keywordPlus | HVAC system | - |
| dc.subject.keywordPlus | In-buildings | - |
| dc.subject.keywordPlus | Inlet air | - |
| dc.subject.keywordPlus | Membrane layers | - |
| dc.subject.keywordPlus | Pump pressures | - |
| dc.subject.keywordPlus | Membranes | - |
| dc.identifier.url | https://www.proquest.com/docview/2699753731/4F19E6F0AFDE4532PQ/1?accountid=11283 | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
222, Wangsimni-ro, Seongdong-gu, Seoul, 04763, Korea+82-2-2220-1366
COPYRIGHT © 2024 HANYANG UNIVERSITY.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.