Applicability performance evaluation of cascade heat pump for building electrification in winter

Full metadata record
DC Field Value Language
dc.contributor.authorKim, Beom-Jun-
dc.contributor.authorKim, Seheon-
dc.contributor.authorGo, Mingeon-
dc.contributor.authorJoo, Hong-Jin-
dc.contributor.authorJeong, Jae-Weon-
dc.date.accessioned2024-11-28T13:31:03Z-
dc.date.available2024-11-28T13:31:03Z-
dc.date.issued2024-04-
dc.identifier.issn2352-7102-
dc.identifier.issn2352-7102-
dc.identifier.urihttps://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/196553-
dc.description.abstractThis study aimed to evaluate the performance of indoor air heating and domestic hot water supply using a cascade heat pump system. The focus was on using existing heat pump equipment to satisfy system requirements in the context of building retrofitting. The experimental setup was located in nearly net-zero experimental building of the South Korea. The system was configured to heat air in the low-cycle heat pump and supply hot domestic water in the high-cycle heat pump. The study compared three operational modes: a low-cycle-only mode; a hot water-only mode; and a combined mode. While low-cycle-only mode and hot-water-only mode fulfilled the required condition with 3.94–5.38 COP and 60 °C hot water temperature with a flow rate of 15.8 LPM separately, the combined mode failed to reach the target air temperature fulfilling only hot water temperature. In conclusion, the system demonstrated satisfactory performance when heating indoor air and providing hot water separately. However, the indoor heating performance declined when both functions were operated simultaneously. To address this issue, possible solutions could include revising the system operation logic to better align with heating and domestic hot water usage schedules or altering the refrigerant flow path.-
dc.format.extent17-
dc.language영어-
dc.language.isoENG-
dc.publisherElsevier BV-
dc.titleApplicability performance evaluation of cascade heat pump for building electrification in winter-
dc.typeArticle-
dc.publisher.location네델란드-
dc.identifier.doi10.1016/j.jobe.2023.108406-
dc.identifier.scopusid2-s2.0-85181164956-
dc.identifier.wosid001165650000001-
dc.identifier.bibliographicCitationJournal of Building Engineering, v.82, pp 1 - 17-
dc.citation.titleJournal of Building Engineering-
dc.citation.volume82-
dc.citation.startPage1-
dc.citation.endPage17-
dc.type.docTypeArticle; Early Access-
dc.description.isOpenAccessN-
dc.description.journalRegisteredClassscie-
dc.description.journalRegisteredClassscopus-
dc.relation.journalResearchAreaConstruction & Building Technology-
dc.relation.journalResearchAreaEngineering-
dc.relation.journalWebOfScienceCategoryConstruction & Building Technology-
dc.relation.journalWebOfScienceCategoryEngineering, Civil-
dc.subject.keywordPlusAir source heat pumps-
dc.subject.keywordPlusPumps-
dc.subject.keywordPlusWater supply-
dc.subject.keywordPlusWater temperature-
dc.subject.keywordAuthorCascade heat pump system-
dc.subject.keywordAuthorField experiment study-
dc.subject.keywordAuthorHeating performance-
dc.subject.keywordAuthorResidential building-
dc.subject.keywordAuthorSystem retrofitting-
dc.identifier.urlhttps://www.sciencedirect.com/science/article/pii/S2352710223025895?via%3Dihub-
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE