Cited 0 time in
A novel real-time method for HVAC system operation to improve indoor environmental quality in meeting rooms
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | Li, Wenzhuo | - |
| dc.contributor.author | Koo, Choongwan | - |
| dc.contributor.author | Cha, Seung Hyun | - |
| dc.contributor.author | Hong, Taehoon | - |
| dc.contributor.author | Oh, Jeongyoon | - |
| dc.date.accessioned | 2024-12-20T07:42:36Z | - |
| dc.date.available | 2024-12-20T07:42:36Z | - |
| dc.date.issued | 2018-10 | - |
| dc.identifier.issn | 0360-1323 | - |
| dc.identifier.issn | 1873-684X | - |
| dc.identifier.uri | https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/203585 | - |
| dc.description.abstract | For indoor environmental quality (IEQ), previous studies only focused on one-sided aspect (e.g. monitoring, diagnostic, or intervention), and have not fully considered excessive pollutants and dew condensation in meeting rooms. Based on a real-time sensor network, this study newly implemented a three-phase cyclic process (i.e. monitoring-diagnostic-intervention process), with which a novel real-time method for HVAC system operation was developed to improve IEQ in meeting rooms. In particular, this study conducted two kinds of analyses and controls: (i) basic analysis and control for excessive pollutants by utilizing temperature and CO2 concentration; and (ii) advanced analysis and control for dew condensation on the diffuser of HVAC system by utilizing temperature, humidity, and CO2 concentration. The main findings were summarized as follows. For the "basic analysis", the CO2 concentration was estimated to exceed 1000 ppm at 14.8% and 3L7% in two meeting rooms. To avoid it, a real-time "basic control" strategy was developed: if the CO2 concentration would exceed 1000 ppm, the ventilation volume of the outdoor air could increase in real time. For the "advanced analysis", dew condensation on the diffuser was estimated to happen at 40.7% and 82.6% in two meeting rooms. To avoid it, a realtime "advanced control" strategy was developed: if the estimated supply air temperature would be lower than the calculated dew-point temperature, the supply-air temperature and ventilation volume of HVAC system could increase. The novel real-time method can be easily applied to HVAC system operation in existing buildings where events are hard to be predicted and recognized. | - |
| dc.format.extent | 21 | - |
| dc.language | 영어 | - |
| dc.language.iso | ENG | - |
| dc.publisher | PERGAMON-ELSEVIER SCIENCE LTD | - |
| dc.title | A novel real-time method for HVAC system operation to improve indoor environmental quality in meeting rooms | - |
| dc.type | Article | - |
| dc.publisher.location | 영국 | - |
| dc.identifier.doi | 10.1016/j.buildenv.2018.08.046 | - |
| dc.identifier.scopusid | 2-s2.0-85052477994 | - |
| dc.identifier.wosid | 000447484300033 | - |
| dc.identifier.bibliographicCitation | BUILDING AND ENVIRONMENT, v.144, pp 365 - 385 | - |
| dc.citation.title | BUILDING AND ENVIRONMENT | - |
| dc.citation.volume | 144 | - |
| dc.citation.startPage | 365 | - |
| dc.citation.endPage | 385 | - |
| dc.type.docType | Article | - |
| dc.description.isOpenAccess | N | - |
| dc.description.journalRegisteredClass | scie | - |
| dc.description.journalRegisteredClass | scopus | - |
| dc.relation.journalResearchArea | Construction & Building Technology | - |
| dc.relation.journalResearchArea | Engineering | - |
| dc.relation.journalWebOfScienceCategory | Construction & Building Technology | - |
| dc.relation.journalWebOfScienceCategory | Engineering, Environmental | - |
| dc.relation.journalWebOfScienceCategory | Engineering, Civil | - |
| dc.subject.keywordPlus | RESIDENTIAL BUILDINGS | - |
| dc.subject.keywordPlus | AIR-TEMPERATURE | - |
| dc.subject.keywordPlus | VENTILATION CONTROL | - |
| dc.subject.keywordPlus | ENERGY-CONSUMPTION | - |
| dc.subject.keywordPlus | CO2 CONCENTRATION | - |
| dc.subject.keywordPlus | THERMAL COMFORT | - |
| dc.subject.keywordPlus | HONG-KONG | - |
| dc.subject.keywordPlus | PERFORMANCE | - |
| dc.subject.keywordPlus | OCCUPANCY | - |
| dc.subject.keywordPlus | CONDENSATION | - |
| dc.subject.keywordAuthor | Real-time big data | - |
| dc.subject.keywordAuthor | Monitoring and diagnostics | - |
| dc.subject.keywordAuthor | Excessive pollutant | - |
| dc.subject.keywordAuthor | Dew condensation | - |
| dc.subject.keywordAuthor | Automatic control | - |
| dc.subject.keywordAuthor | HVAC system | - |
| dc.identifier.url | https://linkinghub.elsevier.com/retrieve/pii/S0360132318305201 | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
222, Wangsimni-ro, Seongdong-gu, Seoul, 04763, Korea+82-2-2220-1366
COPYRIGHT © 2024 HANYANG UNIVERSITY.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.