Cited 0 time in
안내 깃이 장착된 시로코 팬 성능과 내부 유동 연구
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | 이종원 | - |
| dc.contributor.author | 이정수 | - |
| dc.contributor.author | 이현규 | - |
| dc.contributor.author | 조진수 | - |
| dc.date.accessioned | 2021-07-30T04:55:15Z | - |
| dc.date.available | 2021-07-30T04:55:15Z | - |
| dc.date.issued | 2019-06 | - |
| dc.identifier.issn | 2287-9706 | - |
| dc.identifier.uri | https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/2184 | - |
| dc.description.abstract | A sirocco fan with forward-curved blades is mainly used when a high air volume is needed in a confined space. Generally, the efficiency of the sirocco fan is lower than that of the fan having the same size. To increase the efficiency of the sirocco fan, a guide vane was installed in the outlet part of the fan, thereby improving the passage of the airflow. The influence of the air flow by the guide vane was analyzed using computational fluid dynamics. The guide vane reduced the size of the recirculation zone, reduced the power up to 3.37%, and increased the static pressure efficiency. The static pressure efficiency reached the maximum as the chord length increased. The study also demonstrated the highest static pressure efficiency when the guide vane angle was 16~17 degree. | - |
| dc.format.extent | 7 | - |
| dc.language | 한국어 | - |
| dc.language.iso | KOR | - |
| dc.publisher | 한국유체기계학회 | - |
| dc.title | 안내 깃이 장착된 시로코 팬 성능과 내부 유동 연구 | - |
| dc.title.alternative | Study on the Performance and Internal Airflow of the Sirocco Fan with a Guide Vane | - |
| dc.type | Article | - |
| dc.publisher.location | 대한민국 | - |
| dc.identifier.doi | 10.5293/kfma.2019.22.3.012 | - |
| dc.identifier.bibliographicCitation | 한국유체기계학회 논문집, v.22, no.3, pp 12 - 18 | - |
| dc.citation.title | 한국유체기계학회 논문집 | - |
| dc.citation.volume | 22 | - |
| dc.citation.number | 3 | - |
| dc.citation.startPage | 12 | - |
| dc.citation.endPage | 18 | - |
| dc.identifier.kciid | ART002471250 | - |
| dc.description.isOpenAccess | N | - |
| dc.description.journalRegisteredClass | kci | - |
| dc.subject.keywordAuthor | Sirocco Fan(시로코 팬) | - |
| dc.subject.keywordAuthor | Packaged Air Conditioner(패키지 에어컨) | - |
| dc.subject.keywordAuthor | Guide Vane(안내 익) | - |
| dc.subject.keywordAuthor | Fan Laws(팬 법칙) | - |
| dc.subject.keywordAuthor | Recirculation Flow(재순환 유동) | - |
| dc.subject.keywordAuthor | Secondary Flow(이차 유동) | - |
| dc.subject.keywordAuthor | Flow Separation(유동 박리) | - |
| dc.identifier.url | https://www.dbpia.co.kr/journal/articleDetail?nodeId=NODE08757655&language=ko_KR&hasTopBanner=true | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
222, Wangsimni-ro, Seongdong-gu, Seoul, 04763, Korea+82-2-2220-1366
COPYRIGHT © 2024 HANYANG UNIVERSITY.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.