Cited 32 time in
A novel louvered fin design to enhance thermal and drainage performances during periodic frosting/defrosting conditions
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | Kim, Min-Hwan | - |
| dc.contributor.author | Kim, Hisuk | - |
| dc.contributor.author | Kim, Dong Rip | - |
| dc.contributor.author | Lee, Kwan-Soo | - |
| dc.date.accessioned | 2021-08-02T17:34:01Z | - |
| dc.date.available | 2021-08-02T17:34:01Z | - |
| dc.date.issued | 2016-02 | - |
| dc.identifier.issn | 0196-8904 | - |
| dc.identifier.issn | 1879-2227 | - |
| dc.identifier.uri | https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/24031 | - |
| dc.description.abstract | The retention water on fin surface can significantly degrade the thermal performance of heat exchangers under periodic frosting/defrosting conditions, which also leads to a decrease in the energy efficiency of air-source heat pumps. A novel louvered fin design was suggested to improve the drainage and the thermal performance of heat exchanger. The novel louvered fin had an asymmetric louver arrangement by flattening two louvers on the leading edge. The retention water formed on fin surface markedly decreased the heat transfer rate of the conventional symmetric louvered fins in re-frosting cycles. On the other hand, the asymmetric louvered fins improved the drainage performance of the retention water, which enhanced the heat transfer rate. To identify the reason of the difference in drainage performance between two fin geometries, additional experiments were carried out with enlargement models. The improvement in drainage performance of the asymmetric fin design originated from the lowered surface tension between the fin surface and water droplet. | - |
| dc.format.extent | 7 | - |
| dc.language | 영어 | - |
| dc.language.iso | ENG | - |
| dc.publisher | Elsevier | - |
| dc.title | A novel louvered fin design to enhance thermal and drainage performances during periodic frosting/defrosting conditions | - |
| dc.type | Article | - |
| dc.publisher.location | 영국 | - |
| dc.identifier.doi | 10.1016/j.enconman.2015.11.028 | - |
| dc.identifier.scopusid | 2-s2.0-84952886350 | - |
| dc.identifier.wosid | 000369191400048 | - |
| dc.identifier.bibliographicCitation | Energy Conversion and Management, v.110, pp 494 - 500 | - |
| dc.citation.title | Energy Conversion and Management | - |
| dc.citation.volume | 110 | - |
| dc.citation.startPage | 494 | - |
| dc.citation.endPage | 500 | - |
| dc.type.docType | Article | - |
| dc.description.isOpenAccess | N | - |
| dc.description.journalRegisteredClass | scie | - |
| dc.description.journalRegisteredClass | scopus | - |
| dc.relation.journalResearchArea | Thermodynamics | - |
| dc.relation.journalResearchArea | Energy & Fuels | - |
| dc.relation.journalResearchArea | Mechanics | - |
| dc.relation.journalWebOfScienceCategory | Thermodynamics | - |
| dc.relation.journalWebOfScienceCategory | Energy & Fuels | - |
| dc.relation.journalWebOfScienceCategory | Mechanics | - |
| dc.subject.keywordPlus | SOURCE HEAT-PUMP | - |
| dc.subject.keywordPlus | FROSTING CONDITIONS | - |
| dc.subject.keywordPlus | AIR | - |
| dc.subject.keywordPlus | EXCHANGERS | - |
| dc.subject.keywordPlus | SURFACE | - |
| dc.subject.keywordPlus | RETENTION | - |
| dc.subject.keywordPlus | BEHAVIOR | - |
| dc.subject.keywordPlus | CYCLES | - |
| dc.subject.keywordPlus | SYSTEM | - |
| dc.subject.keywordPlus | PLAIN | - |
| dc.subject.keywordAuthor | Frost formation | - |
| dc.subject.keywordAuthor | Defrosting | - |
| dc.subject.keywordAuthor | Water retention | - |
| dc.subject.keywordAuthor | Drainage | - |
| dc.subject.keywordAuthor | Louvered fin | - |
| dc.subject.keywordAuthor | Air source heat pump | - |
| dc.identifier.url | https://www.sciencedirect.com/science/article/pii/S0196890415010481?via%3Dihub | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
222, Wangsimni-ro, Seongdong-gu, Seoul, 04763, Korea+82-2-2220-1366
COPYRIGHT © 2024 HANYANG UNIVERSITY.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.