Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Corrosion Performance of Cu Bonded Grounding-Electrode by Accelerated Corrosion Test

Full metadata record
DC Field Value Language
dc.contributor.authorChoi, Sun Kyu-
dc.contributor.authorKim, Kyung Chul-
dc.date.available2021-03-17T08:42:08Z-
dc.date.created2020-07-06-
dc.date.issued2018-10-31-
dc.identifier.issn1598-6462-
dc.identifier.urihttps://scholarworks.bwise.kr/hongik/handle/2020.sw.hongik/12995-
dc.description.abstractNatural degradation of grounding-electrode in soil environment should be monitored for several decades to predict the lifetime of the grounding electrode for efficient application and management. However, long-term studies for such electrodes have many practical limitations. The conventional accelerated corrosion test is unsuitable for such studies because simulated soil corrosion process cannot represent the actual soil environment. A preliminary experiment of accelerated corrosion test was conducted using existing test standards. The accelerated corrosion test that reflects the actual soil environment has been developed to evaluate corrosion performances of grounding-electrodes in a short period. Several test conditions with different chamber temperatures and salt spray were used to imitate actual field conditions based on ASTM B162, ASTM B117, and ISO 14993 standards. Accelerated degradation specimens of copper-bonded electrodes were made by the facile method and their corrosion performances were investigated. Their corrosion rates were calculated to 0.042 mu m/day, 0.316 mu m/day, and 0.11 mu m/day, respectively. These results indicate that accelerated deterioration of grounding materials can be determined in a short period by using cyclic test condition with salt spray temperature of 50 degrees C.-
dc.language영어-
dc.language.isoen-
dc.publisherCORROSION SCIENCE SOC KOREA-
dc.titleCorrosion Performance of Cu Bonded Grounding-Electrode by Accelerated Corrosion Test-
dc.typeArticle-
dc.contributor.affiliatedAuthorKim, Kyung Chul-
dc.identifier.doi10.14773/cst.2018.17.5.211-
dc.identifier.wosid000454741900002-
dc.identifier.bibliographicCitationCORROSION SCIENCE AND TECHNOLOGY-KOREA, v.17, no.5, pp.211 - 217-
dc.relation.isPartOfCORROSION SCIENCE AND TECHNOLOGY-KOREA-
dc.citation.titleCORROSION SCIENCE AND TECHNOLOGY-KOREA-
dc.citation.volume17-
dc.citation.number5-
dc.citation.startPage211-
dc.citation.endPage217-
dc.type.rimsART-
dc.type.docTypeArticle-
dc.identifier.kciidART002398934-
dc.description.journalClass2-
dc.description.journalRegisteredClasskci-
dc.description.journalRegisteredClassother-
dc.relation.journalResearchAreaElectrochemistry-
dc.relation.journalWebOfScienceCategoryElectrochemistry-
dc.subject.keywordAuthorCorrosion accelerated test-
dc.subject.keywordAuthorSoil corrosion-
dc.subject.keywordAuthorGrounding rods-
dc.subject.keywordAuthorCopper-bonded electrode-
dc.subject.keywordAuthorLife cycle estimation-
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Science and Technology > Department of Electronic and Electrical Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.