냉복도 밀폐시스템의 적용에 의한 데이터센터 서버실의 냉방에너지 절감 효과 분석
DC Field | Value | Language |
---|---|---|
dc.contributor.author | 장현재 | - |
dc.contributor.author | 정용호 | - |
dc.contributor.author | 서장후 | - |
dc.date.accessioned | 2021-12-02T05:43:36Z | - |
dc.date.available | 2021-12-02T05:43:36Z | - |
dc.date.created | 2021-11-29 | - |
dc.date.issued | 2012 | - |
dc.identifier.issn | 1976-6483 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/hongik/handle/2020.sw.hongik/19353 | - |
dc.description.abstract | In order to keep the server room temperature condition, energy consumption has been rapidly increased as the increasing internal heat gain of server room in data center. And the cooling units for server systems are fully operated to satisfy the indoor temperature condition, it results in the excessive energy consumption. There are many wastes of cooling energy which is caused by the structural problems in data center server room. For example, a leakage by the electric cable hole, mixing or recirculation of hot air from the hot aisle to the cold aisle, short circulation of the CRAC(Computer Room Air Conditioning), and others. So there are many strategies to reduce the waste of cooling energy in data center. In this study, cold aisle containment system was proposed among the various strategies to reduce the waste energy by recirculation air from the hot aisle. To verify the effectiveness of the cold aisle containment system, test bed which is same with exist server room was set up in IDC(Internet Data Center) building. And comparative experiments, conventional open type cooling system and cold aisle containment sysetm, were carried out in actual conditions. As the result, the range of inlet temperature of server system was 20~25℃ in exist cooling system and the range of inlet temperature dropped below 20℃ by cold aisle containment system. After all, was possible by the cold aisle containment system and cold aisle containment system was proved to be the solution for energy saving cooling system. | - |
dc.language | 한국어 | - |
dc.language.iso | ko | - |
dc.publisher | 한국건축친환경설비학회 | - |
dc.title | 냉복도 밀폐시스템의 적용에 의한 데이터센터 서버실의 냉방에너지 절감 효과 분석 | - |
dc.title.alternative | Analysis of Cooling Energy Saving by Cold Aisle Containment System in Internet Data Center Server Room | - |
dc.type | Article | - |
dc.contributor.affiliatedAuthor | 장현재 | - |
dc.identifier.bibliographicCitation | 한국건축친환경설비학회 논문집, v.6, no.3, pp.181 - 190 | - |
dc.relation.isPartOf | 한국건축친환경설비학회 논문집 | - |
dc.citation.title | 한국건축친환경설비학회 논문집 | - |
dc.citation.volume | 6 | - |
dc.citation.number | 3 | - |
dc.citation.startPage | 181 | - |
dc.citation.endPage | 190 | - |
dc.type.rims | ART | - |
dc.identifier.kciid | ART001700568 | - |
dc.description.journalClass | 2 | - |
dc.description.journalRegisteredClass | kci | - |
dc.description.journalRegisteredClass | other | - |
dc.subject.keywordAuthor | CRAC | - |
dc.subject.keywordAuthor | Data center | - |
dc.subject.keywordAuthor | Energy cost | - |
dc.subject.keywordAuthor | Cold aisle containment system | - |
dc.subject.keywordAuthor | Re-circulation air | - |
dc.subject.keywordAuthor | Cold aisle | - |
dc.subject.keywordAuthor | 항온항습기 | - |
dc.subject.keywordAuthor | 데이터 센터 | - |
dc.subject.keywordAuthor | 에너지 비용 | - |
dc.subject.keywordAuthor | 밀폐형 쿨링시스템 | - |
dc.subject.keywordAuthor | 재순환공기 | - |
dc.subject.keywordAuthor | 냉복도 | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
94, Wausan-ro, Mapo-gu, Seoul, 04066, Korea02-320-1314
COPYRIGHT 2020 HONGIK UNIVERSITY. ALL RIGHTS RESERVED.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.