배전계통에 사용되는 봉형 접지전극의 접지 특성 분석
DC Field | Value | Language |
---|---|---|
dc.contributor.author | 김경철 | - |
dc.contributor.author | 정지원 | - |
dc.date.accessioned | 2021-12-15T03:43:53Z | - |
dc.date.available | 2021-12-15T03:43:53Z | - |
dc.date.created | 2021-12-10 | - |
dc.date.issued | 2011 | - |
dc.identifier.issn | 1229-4691 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/hongik/handle/2020.sw.hongik/20275 | - |
dc.description.abstract | Grounding system insures a reference potential point for electric devices and also provides a low impedance path for fault currents or transient currents in the earth. The ground impedance as function of frequency is necessary for determining its performance since fault currents could contain a wide range of frequencies. In this paper, the grounding resistance, grounding impedance and transient grounding impedance are measured by using 3-point fall-of-potential method in order to analyse grounding characteristics of the copper and concrete rod grounding electrodes. An equivalent transfer function model of the ground impedance and transient grounding impedance are identified from the measured values by using ARMA method and evaluated by comparing the conventional grounding impedance. | - |
dc.language | 한국어 | - |
dc.language.iso | ko | - |
dc.publisher | 한국조명.전기설비학회 | - |
dc.title | 배전계통에 사용되는 봉형 접지전극의 접지 특성 분석 | - |
dc.title.alternative | Grounding Characteristics Analysis of the Rod-Type Grounding Electrodes used for Electric Distribution Systems | - |
dc.type | Article | - |
dc.contributor.affiliatedAuthor | 김경철 | - |
dc.identifier.bibliographicCitation | 조명.전기설비학회논문지, v.25, no.6, pp.49 - 56 | - |
dc.relation.isPartOf | 조명.전기설비학회논문지 | - |
dc.citation.title | 조명.전기설비학회논문지 | - |
dc.citation.volume | 25 | - |
dc.citation.number | 6 | - |
dc.citation.startPage | 49 | - |
dc.citation.endPage | 56 | - |
dc.type.rims | ART | - |
dc.identifier.kciid | ART001559919 | - |
dc.description.journalClass | 2 | - |
dc.description.journalRegisteredClass | kci | - |
dc.subject.keywordAuthor | Copper Rod | - |
dc.subject.keywordAuthor | Concrete Rod | - |
dc.subject.keywordAuthor | Grounding Resistance | - |
dc.subject.keywordAuthor | Grounding Impedance | - |
dc.subject.keywordAuthor | Frequency and Time Domain Characteristics Test | - |
dc.subject.keywordAuthor | Copper Rod | - |
dc.subject.keywordAuthor | Concrete Rod | - |
dc.subject.keywordAuthor | Grounding Resistance | - |
dc.subject.keywordAuthor | Grounding Impedance | - |
dc.subject.keywordAuthor | Frequency and Time Domain Characteristics Test | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
94, Wausan-ro, Mapo-gu, Seoul, 04066, Korea02-320-1314
COPYRIGHT 2020 HONGIK UNIVERSITY. ALL RIGHTS RESERVED.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.