Evaluation of grounding performance of energized substation by ground current measurement

Authors
Choi, J. K.Ahn, Y. H.Woo, J. W.Jung, G. J.Han, B. S.Kim, K. C.
Issue Date
Sep-2007
Publisher
ELSEVIER SCIENCE SA
Keywords
ground resistance; grounding system; substation; fall-of-potential method
Citation
ELECTRIC POWER SYSTEMS RESEARCH, v.77, no.11, pp.1490 - 1494
Journal Title
ELECTRIC POWER SYSTEMS RESEARCH
Volume
77
Number
11
Start Page
1490
End Page
1494
URI
https://scholarworks.bwise.kr/hongik/handle/2020.sw.hongik/23546
DOI
10.1016/j.epsr.2006.08.028
ISSN
0378-7796
Abstract
Substation grounding systems typically build up a large network of various grounding electrodes, which consists of a substation grounding grid, multi-grounded transmission line skywires and distribution line neutral wires. Although the fall-of-potential (FOP) method has been widely used for ground resistance measurement, it is difficult to use the method in case of such a substation grounding system because of the difficulty of interpretation of the measured FOP profile. In this paper, we have presented a practical example of ground resistance measurement in a 154 kV substation under commercial operating condition. Conventional FOP tests and the measurement of ground current splits to each part of the grounding system were conducted simultaneously. A simple interpretation method of FOP profiles, with the measured ground current splits, has been suggested. (C) 2006 Elsevier B.V. All rights reserved.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Science and Technology > Department of Electronic and Electrical Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Altmetrics

Total Views & Downloads

BROWSE