Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

접지전류 측정에 의한 다중 접지계통의 접지저항 측정Measurement of Resistance of Multi-Grounded System by Ground Current Measurement

Other Titles
Measurement of Resistance of Multi-Grounded System by Ground Current Measurement
Authors
최종기안용호정길조한병성김경철
Issue Date
2004
Publisher
대한전기학회
Keywords
접지전류; 접지저항; 다중접지; 분류계수
Citation
전기학회논문지 A권, v.53, no.4(A), pp.234 - 237
Journal Title
전기학회논문지 A권
Volume
53
Number
4(A)
Start Page
234
End Page
237
URI
https://scholarworks.bwise.kr/hongik/handle/2020.sw.hongik/26370
ISSN
1229-2443
Abstract
Measuring ground resistance has been a popular method of evaluation of the grounding electrode performance. If some portions of grounding electrodes are lost by corrosion, aging or other reasons, consequent deteriotation of the grounding performance would be resulted. It is one of the reasons why it is required to evaluate the performance of grounding systems regularly. However, in case of the electric facilities with multi-grounded system such as power substations with multi-grounded overhead ground wires and/or distribution line neutrals, it is practically difficult to disconnect neutrals or skywires from the substation grounding mesh for the ground resistance measurement. In this paper, a method for the grounding performance measurement of multi-grounded systems, which is based on the measuring ground current distributions, has been proposed. A field test results has shown the validity of the proposed test method.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Science and Technology > Department of Electronic and Electrical Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Altmetrics

Total Views & Downloads

BROWSE