Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

데이터센터의 급기온도 변화가 서버 냉각 성능에 미치는 영향에 대한 연구

Full metadata record
DC Field Value Language
dc.contributor.author장현재-
dc.date.available2020-07-10T04:36:04Z-
dc.date.created2020-07-06-
dc.date.issued2018-
dc.identifier.issn1229-6422-
dc.identifier.urihttps://scholarworks.bwise.kr/hongik/handle/2020.sw.hongik/4697-
dc.description.abstractA datacenter is a high energy consuming facility whose cooling energy consumption rate is 10~20 times larger than general office buildings. The higher the temperature of supply air from a CRAC (computer room air- conditioner) is supplied, the more energy efficient cooling is possible because of improving the COP of a chiller and advanced range of outdoor air temperature available for the economizer cycles. However, because the temperature of cold air flowing into server computers varies depending on air mixing configurations in a computer room, the proper supply air temperature must be considered based on the investigation of air mixing and heat dissipation. By these, this study aims to understand the effects of variation of the supply air temperature on the air flow distributions, temperature distributions and rack cooling efficiencies. Computational fluid dynamics (CFD) aided in conducting the investigation. As a result, the variation of the supply air temperature does not affect the air flow distributions. However, it mainly affects the temperature distribution. From the results of CFD simulations, Rack cooling indices (RCIHI and RCILO) were evaluated and showed the ideal state set at 19℃ of the supply air temperature.-
dc.language한국어-
dc.language.isoko-
dc.publisher대한설비공학회-
dc.title데이터센터의 급기온도 변화가 서버 냉각 성능에 미치는 영향에 대한 연구-
dc.title.alternativeA Study on the Effects of Supply Air Temperature on the Server Cooling Performance in a Data Center-
dc.typeArticle-
dc.contributor.affiliatedAuthor장현재-
dc.identifier.doi10.6110/KJACR.2018.30.2.083-
dc.identifier.bibliographicCitation설비공학 논문집, v.30, no.2, pp.83 - 91-
dc.relation.isPartOf설비공학 논문집-
dc.citation.title설비공학 논문집-
dc.citation.volume30-
dc.citation.number2-
dc.citation.startPage83-
dc.citation.endPage91-
dc.type.rimsART-
dc.identifier.kciidART002314371-
dc.description.journalClass2-
dc.description.journalRegisteredClasskci-
dc.subject.keywordAuthorData center(데이터센터)-
dc.subject.keywordAuthorSupply air temperature(급기온도)-
dc.subject.keywordAuthorRack cooling index(RCI-
dc.subject.keywordAuthor랙 냉각 지표)-
dc.subject.keywordAuthorReturn temperature index(RTI-
dc.subject.keywordAuthor환기온도 지표)-
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Science and Technology > Major in Architecture Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Chang, Hyun jae photo

Chang, Hyun jae
Science & Technology (Architectural Engineering)
Read more

Altmetrics

Total Views & Downloads

BROWSE