두번의 퀜치를 갖는 초전도한류기의 동작특성 및 전력부담 분석Analysis on Operating Characteristics and Power Burden of SFCL with Twice Quench
- Other Titles
- Analysis on Operating Characteristics and Power Burden of SFCL with Twice Quench
- Authors
- 임승택; 고주찬; 나승성; 임성훈
- Issue Date
- Jul-2016
- Publisher
- 한국조명.전기설비학회
- Keywords
- Superconducting Fault Current Limiter (SFCL); Operating Characteristics; Power Burden; Double Quench
- Citation
- 조명.전기설비학회논문지, v.30, no.7, pp.41 - 46
- Journal Title
- 조명.전기설비학회논문지
- Volume
- 30
- Number
- 7
- Start Page
- 41
- End Page
- 46
- URI
- http://scholarworks.bwise.kr/ssu/handle/2018.sw.ssu/8268
- ISSN
- 1229-4691
- Abstract
- SFCL(superconducting Fault Current Limiter) which had zero impedance characteristic does not have power loss and limits quickly fault current. So it plays a rule as a protective equipment. And there are many type of SFCL. In this paper, we analyzed a SFCL with twice Quench so as to improve existing SFCL that operates regardless of scale of fault current. This SFCL with twice quench composed of extra series resistance(RS) and could limit once or twice dependent on scale of fault current. We analyzed operating characteristics and power burden of SFCL and its components according to fault position and series resistance(RS). Through the analysis, we could confirm that SFCL with RS operated at lower current, limited the fault current faster. And components’s power burden could be analyzed.
- Files in This Item
-
Go to Link
- Appears in
Collections - College of Engineering > School of Electrical Engineering > 1. Journal Articles
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.