바닥 복사 난방시스템에서 PCM 적용에 따른 Mock-up 실험
DC Field | Value | Language |
---|---|---|
dc.contributor.author | Kim, Tae Won | - |
dc.contributor.author | Yang, Young Kwon | - |
dc.contributor.author | Kim, Hwan-Sik | - |
dc.contributor.author | Park. Jin Chul | - |
dc.date.available | 2019-03-08T05:36:42Z | - |
dc.date.issued | 2018-11 | - |
dc.identifier.issn | 1229-6422 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/cau/handle/2019.sw.cau/2391 | - |
dc.description.abstract | This study represent an experimental study of PCM floor radiant heating system. The results obtained from the study are summarized as follows; 1) PCM floor radiant heating system is an insertion of a 10 mm thick PCM into the existing standard floor structure, which has the advantage of good construct ability due to no additional process. 2) It was confirmed that the PCM thread remains higher than the normal room. In particular, it was found that the temperature of hot water pipes under the pipes was maintained at 36℃ or higher after four hours after the boiler was stopped. Therefore, we have seen that the room temperature of the PCM floor radiant heating system is longer than the general floor heating system, PCM Floor Radiant Heating is considered to improve the comfort of indoor residents. | - |
dc.description.abstract | This study represent an experimental study of PCM floor radiant heating system. The results obtained from the study are summarized as follows; 1) PCM floor radiant heating system is an insertion of a 10 mm thick PCM into the existing standard floor structure, which has the advantage of good construct ability due to no additional process. 2) It was confirmed that the PCM thread remains higher than the normal room. In particular, it was found that the temperature of hot water pipes under the pipes was maintained at 36℃ or higher after four hours after the boiler was stopped. Therefore, we have seen that the room temperature of the PCM floor radiant heating system is longer than the general floor heating system, PCM Floor Radiant Heating is considered to improve the comfort of indoor residents. | - |
dc.format.extent | 11 | - |
dc.publisher | 대한설비공학회 | - |
dc.title | 바닥 복사 난방시스템에서 PCM 적용에 따른 Mock-up 실험 | - |
dc.title.alternative | Mock-up Test Applicate to Phase Change Material in Floor Radiant Heating System | - |
dc.type | Article | - |
dc.identifier.doi | 10.6110/KJACR.2018.30.11.497 | - |
dc.identifier.bibliographicCitation | 설비공학 논문집, v.30, no.11, pp 497 - 507 | - |
dc.identifier.kciid | ART002401771 | - |
dc.description.isOpenAccess | N | - |
dc.citation.endPage | 507 | - |
dc.citation.number | 11 | - |
dc.citation.startPage | 497 | - |
dc.citation.title | 설비공학 논문집 | - |
dc.citation.volume | 30 | - |
dc.publisher.location | 대한민국 | - |
dc.subject.keywordAuthor | Floor radiant heating | - |
dc.subject.keywordAuthor | Phase change material | - |
dc.subject.keywordAuthor | Mock-up | - |
dc.subject.keywordAuthor | 바닥 복사 난방 | - |
dc.subject.keywordAuthor | 상변화물질 | - |
dc.subject.keywordAuthor | 실물모형 | - |
dc.description.journalRegisteredClass | kci | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
84, Heukseok-ro, Dongjak-gu, Seoul, Republic of Korea (06974)02-820-6194
COPYRIGHT 2019 Chung-Ang University All Rights Reserved.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.