냉각탑 주위의 장애물에 의한 재순환 현상에 관한 수치해석
DC Field | Value | Language |
---|---|---|
dc.contributor.author | 이정희 | - |
dc.contributor.author | 최영기 | - |
dc.date.available | 2019-07-18T03:02:14Z | - |
dc.date.issued | 2006 | - |
dc.identifier.issn | 1229-6422 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/cau/handle/2019.sw.cau/29017 | - |
dc.description.abstract | The present study has been conducted to examine the effect of obstacles around a cooling tower and an air-guide to prevent recirculation. In order to analyze the interaction between external flow and cooling tower exit flow, the external region as well as the coolingtower are included in computational domain. Two dimensional analysis is performed using the finite volume method with non-orthogonal and unstructured grid system. The standard turbulence model is used. To investigate the recirculation phenomena, flow and temperature fields are calculated with three approaches such as, the distance between cooling tower and obstacle, the allocated geometrical type, and the effect of height of obstacle. In addition, the air-guide is considered in the current computation. The mean recirculation rate increases with the height of obstacle. The effect of air-guide to reduce the mean recirculation rate is obviously observed. | - |
dc.format.extent | 9 | - |
dc.publisher | 대한설비공학회 | - |
dc.title | 냉각탑 주위의 장애물에 의한 재순환 현상에 관한 수치해석 | - |
dc.title.alternative | Numerical Analysis on Recirculation Generated by Obstacles around a Cooling Tower | - |
dc.type | Article | - |
dc.identifier.bibliographicCitation | 설비공학 논문집, v.18, no.7, pp 578 - 586 | - |
dc.identifier.kciid | ART001016861 | - |
dc.description.isOpenAccess | N | - |
dc.citation.endPage | 586 | - |
dc.citation.number | 7 | - |
dc.citation.startPage | 578 | - |
dc.citation.title | 설비공학 논문집 | - |
dc.citation.volume | 18 | - |
dc.publisher.location | 대한민국 | - |
dc.subject.keywordAuthor | Recirculation | - |
dc.subject.keywordAuthor | Obstacle | - |
dc.subject.keywordAuthor | Cooling tower | - |
dc.subject.keywordAuthor | Air-guide | - |
dc.subject.keywordAuthor | 재순환 | - |
dc.subject.keywordAuthor | 장애물 | - |
dc.subject.keywordAuthor | 냉각탑 | - |
dc.subject.keywordAuthor | 에어가이드 | - |
dc.description.journalRegisteredClass | kci | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
84, Heukseok-ro, Dongjak-gu, Seoul, Republic of Korea (06974)02-820-6194
COPYRIGHT 2019 Chung-Ang University All Rights Reserved.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.