섬식 지하철역사내 화재시 연기제어에 관한 수치해석적 연구
DC Field | Value | Language |
---|---|---|
dc.contributor.author | 이성룡 | - |
dc.contributor.author | 유홍선 | - |
dc.date.available | 2019-07-24T03:04:10Z | - |
dc.date.issued | 2007 | - |
dc.identifier.issn | 1738-6225 | - |
dc.identifier.issn | 2288-2235 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/cau/handle/2019.sw.cau/30029 | - |
dc.description.abstract | In this study, numerical simulations were carried out to analyze the effect of the smoke extraction system and fire shutters in subway station fires using FDS 4.0. Subway station used in the experiment was 145 m long. Simulation results are validated by comparing with experimental results. Simulation results showed good agreement with experimental results within 10℃. 10 MW polystyrene was used as a fuel in the numerical prediction. Numerical predictions were performed in the center-platform type subway station in case of a kiosk fire. Temperature and CO concentration were lowered by the operation of smoke extraction system. But, the operation of fire shutters had little effect on temperature and CO concentration in the platform level. | - |
dc.format.extent | 6 | - |
dc.publisher | 한국철도학회 | - |
dc.title | 섬식 지하철역사내 화재시 연기제어에 관한 수치해석적 연구 | - |
dc.title.alternative | A Numerical Study on the Smoke Control in Center-Platform Type Subway Station Fires | - |
dc.type | Article | - |
dc.identifier.bibliographicCitation | 한국철도학회논문집, v.10, no.3, pp 313 - 318 | - |
dc.identifier.kciid | ART001058532 | - |
dc.description.isOpenAccess | N | - |
dc.citation.endPage | 318 | - |
dc.citation.number | 3 | - |
dc.citation.startPage | 313 | - |
dc.citation.title | 한국철도학회논문집 | - |
dc.citation.volume | 10 | - |
dc.publisher.location | 대한민국 | - |
dc.subject.keywordAuthor | 지하철역사화재 | - |
dc.subject.keywordAuthor | 연기거동 | - |
dc.subject.keywordAuthor | 배연 | - |
dc.subject.keywordAuthor | 방화셔터 | - |
dc.subject.keywordAuthor | Subway station fire | - |
dc.subject.keywordAuthor | Smoke movement | - |
dc.subject.keywordAuthor | Smoke extraction | - |
dc.subject.keywordAuthor | Fire shutter | - |
dc.description.journalRegisteredClass | kci | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
84, Heukseok-ro, Dongjak-gu, Seoul, Republic of Korea (06974)02-820-6194
COPYRIGHT 2019 Chung-Ang University All Rights Reserved.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.