온수배관의 설치 위치에 따른 단열재 표면온도 및 에너지 손실량 비교
DC Field | Value | Language |
---|---|---|
dc.contributor.author | Kim, Seong Eun | - |
dc.contributor.author | Song, Yong Woo | - |
dc.contributor.author | Park, Jin Chul | - |
dc.date.accessioned | 2021-05-20T05:41:19Z | - |
dc.date.available | 2021-05-20T05:41:19Z | - |
dc.date.issued | 2021 | - |
dc.identifier.issn | 1229-6422 | - |
dc.identifier.issn | 2465-7611 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/cau/handle/2019.sw.cau/43978 | - |
dc.description.abstract | In this study, we compared standards for improving the performance of pipes based on their location to better the energy efficiency of buildings. We performed a simulated comparative analysis by measuring the temperature of each installed pipe and applying the insulation-thickness standard used at home and abroad. The pipe shaft located indoors maintained an almost constant temperature, but the pipe installed in an underground parking space was greatly affected by the outside temperature. In winter, the average temperatures of the inside pipe shaft and the one on the first-basement floor were 25.5℃ and 3.3℃, respectively. The simulation analysis for each insulation-thickness criterion showed that the heat loss decreased by 1.7~2.2% when the overseas standard was applied. The analysis of the two installation locations showed that the average heat loss of the pipe installed in the underground parking space was 36.7% greater than that of the pipe that was installed indoors. | - |
dc.format.extent | 6 | - |
dc.language | 한국어 | - |
dc.language.iso | KOR | - |
dc.publisher | 대한설비공학회 | - |
dc.title | 온수배관의 설치 위치에 따른 단열재 표면온도 및 에너지 손실량 비교 | - |
dc.title.alternative | Comparison of Insulation Surface Temperature and Energy Loss Based on the Location of a Hot-Water Pipe | - |
dc.type | Article | - |
dc.identifier.doi | 10.6110/KJACR.2021.33.1.025 | - |
dc.identifier.bibliographicCitation | 설비공학 논문집, v.33, no.1, pp 25 - 30 | - |
dc.identifier.kciid | ART002673782 | - |
dc.description.isOpenAccess | Y | - |
dc.citation.endPage | 30 | - |
dc.citation.number | 1 | - |
dc.citation.startPage | 25 | - |
dc.citation.title | 설비공학 논문집 | - |
dc.citation.volume | 33 | - |
dc.publisher.location | 대한민국 | - |
dc.subject.keywordAuthor | Hot water pipe location | - |
dc.subject.keywordAuthor | Energy loss | - |
dc.subject.keywordAuthor | Insulation surface temperature | - |
dc.subject.keywordAuthor | Simulation | - |
dc.subject.keywordAuthor | 온수배관 설치 위치 | - |
dc.subject.keywordAuthor | 에너지 손실 | - |
dc.subject.keywordAuthor | 단열재 표면온도 | - |
dc.subject.keywordAuthor | 시뮬레이션 | - |
dc.description.journalRegisteredClass | kci | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
84, Heukseok-ro, Dongjak-gu, Seoul, Republic of Korea (06974)02-820-6194
COPYRIGHT 2019 Chung-Ang University All Rights Reserved.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.