Comparisons of performance and operation characteristics for closed- and open-loop passive containment cooling system design
DC Field | Value | Language |
---|---|---|
dc.contributor.author | Bang, J. | - |
dc.contributor.author | Jerng, D.-W. | - |
dc.contributor.author | Kim, H. | - |
dc.date.accessioned | 2021-07-16T05:41:18Z | - |
dc.date.available | 2021-07-16T05:41:18Z | - |
dc.date.issued | 2021-08 | - |
dc.identifier.issn | 1738-5733 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/cau/handle/2019.sw.cau/47588 | - |
dc.description.abstract | Passive containment cooling systems (PCCSs) have been actively studied to improve the inherent safety of nuclear power plants. Hered, we present two concepts, open-loop PCCS (OL-PCCS) and closed-loop PCCS (CL-PCCS), applicable to the PWR with a concrete-type containment. We analyzed the heat-removal performance and flow instability of these PCCS concepts using the GOTHIC code. In both cases, PCCS performance improved when a passive containment cooling heat exchanger (PCCX) was installed in the lower part of the containment building. The OL-PCCS was found to be superior in terms of heat-removal performance. However, in terms of flow instability, the OL-PCCS was more vulnerable than the CL-PCCS. In particular, the possibility of flow instability was higher when the PCCX was installed in the upper part of the containment. Therefore, the installation location of the OL-PCCS should be restricted to minimize flow instability. Conversely, a CL-PCCS can be installed without any positional restriction by adjusting the initial system pressure within the loop, which eliminates flow instability. These results could be used as base data for the thermo-hydraulic evaluation of PCCS in PWR with a large dry concrete-type containment. © 2021 | - |
dc.format.extent | 10 | - |
dc.language | 영어 | - |
dc.language.iso | ENG | - |
dc.publisher | Korean Nuclear Society | - |
dc.title | Comparisons of performance and operation characteristics for closed- and open-loop passive containment cooling system design | - |
dc.title.alternative | Comparisons of performance and operation characteristics for closed- and open-loop passive containment cooling system design | - |
dc.type | Article | - |
dc.identifier.doi | 10.1016/j.net.2021.01.039 | - |
dc.identifier.bibliographicCitation | Nuclear Engineering and Technology, v.53, no.8, pp 2499 - 2508 | - |
dc.identifier.kciid | ART002739044 | - |
dc.description.isOpenAccess | N | - |
dc.identifier.wosid | 000671556200007 | - |
dc.identifier.scopusid | 2-s2.0-85101418167 | - |
dc.citation.endPage | 2508 | - |
dc.citation.number | 8 | - |
dc.citation.startPage | 2499 | - |
dc.citation.title | Nuclear Engineering and Technology | - |
dc.citation.volume | 53 | - |
dc.type.docType | Article | - |
dc.publisher.location | 대한민국 | - |
dc.subject.keywordAuthor | Flow instability | - |
dc.subject.keywordAuthor | GOTHIC code | - |
dc.subject.keywordAuthor | Passive containment cooling systems | - |
dc.subject.keywordPlus | 2-PHASE FLOW INSTABILITY | - |
dc.subject.keywordPlus | APR PLUS | - |
dc.subject.keywordPlus | HEAT | - |
dc.subject.keywordPlus | OSCILLATION | - |
dc.subject.keywordPlus | VALIDATION | - |
dc.subject.keywordPlus | STABILITY | - |
dc.subject.keywordPlus | REACTOR | - |
dc.subject.keywordPlus | CODE | - |
dc.relation.journalResearchArea | Nuclear Science & Technology | - |
dc.relation.journalWebOfScienceCategory | Nuclear Science & Technology | - |
dc.description.journalRegisteredClass | scie | - |
dc.description.journalRegisteredClass | scopus | - |
dc.description.journalRegisteredClass | kci | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
84, Heukseok-ro, Dongjak-gu, Seoul, Republic of Korea (06974)02-820-6194
COPYRIGHT 2019 Chung-Ang University All Rights Reserved.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.