Adaptive control algorithm with a retraining technique to predict the optimal amount of chilled water in a data center cooling system
DC Field | Value | Language |
---|---|---|
dc.contributor.author | Park, B.R. | - |
dc.contributor.author | Choi, Y.J. | - |
dc.contributor.author | Choi, E.J. | - |
dc.contributor.author | Moon, Jin Woo | - |
dc.date.accessioned | 2022-02-25T06:40:07Z | - |
dc.date.available | 2022-02-25T06:40:07Z | - |
dc.date.issued | 2022-06 | - |
dc.identifier.issn | 2352-7102 | - |
dc.identifier.issn | 2352-7102 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/cau/handle/2019.sw.cau/55324 | - |
dc.description.abstract | We developed control algorithms based on one of three artificial-intelligence-based retraining techniques (sliding window, vector adaptation, and vector augmentation) to provide the optimal indoor temperature and save on the energy expenditure for cooling in data centers. The artificial neural network prediction model predicts the computer room air handler supply air temperature of a central chilled water system and is added to the control algorithm. The proposed algorithm can determine the optimal chilled water flow rate required to cool the server to the set temperature by using the predicted computer room air handler supply air temperature. We developed a control algorithm embedded in an artificial neural network predictive model that includes three retraining techniques. Afterward, we compared the control performance and verified its adaptability by using computer simulation. When using the algorithm with sliding window control, the root mean-squared error between the set temperature and the control temperature was 0.08 °C, the maximum error was 0.81 °C, and the cooling load was 21,026.27 kWh. The accuracy, stability, and energy-saving ability of the sliding window control algorithm were higher those of the other two algorithms, and its superior adaptability and scalability under changing environmental conditions were demonstrated. © 2022 Elsevier Ltd | - |
dc.language | 영어 | - |
dc.language.iso | ENG | - |
dc.publisher | Elsevier Ltd | - |
dc.title | Adaptive control algorithm with a retraining technique to predict the optimal amount of chilled water in a data center cooling system | - |
dc.type | Article | - |
dc.identifier.doi | 10.1016/j.jobe.2022.104167 | - |
dc.identifier.bibliographicCitation | Journal of Building Engineering, v.50 | - |
dc.description.isOpenAccess | N | - |
dc.identifier.wosid | 000819832700007 | - |
dc.identifier.scopusid | 2-s2.0-85124280085 | - |
dc.citation.title | Journal of Building Engineering | - |
dc.citation.volume | 50 | - |
dc.type.docType | Article | - |
dc.publisher.location | 네델란드 | - |
dc.subject.keywordAuthor | Artificial neural network | - |
dc.subject.keywordAuthor | Chilled water mass flow control | - |
dc.subject.keywordAuthor | Cooling energy | - |
dc.subject.keywordAuthor | Data center | - |
dc.subject.keywordAuthor | Retraining | - |
dc.subject.keywordPlus | ENERGY PERFORMANCE | - |
dc.subject.keywordPlus | OPTIMIZATION | - |
dc.subject.keywordPlus | MODEL | - |
dc.subject.keywordPlus | FLOW | - |
dc.relation.journalResearchArea | Construction & Building Technology | - |
dc.relation.journalResearchArea | Engineering | - |
dc.relation.journalWebOfScienceCategory | Construction & Building Technology | - |
dc.relation.journalWebOfScienceCategory | Engineering, Civil | - |
dc.description.journalRegisteredClass | scie | - |
dc.description.journalRegisteredClass | scopus | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
84, Heukseok-ro, Dongjak-gu, Seoul, Republic of Korea (06974)02-820-6194
COPYRIGHT 2019 Chung-Ang University All Rights Reserved.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.