Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

An Online UPS System That Eliminates the Inrush Current Phenomenon While Feeding Multiple Load Transformers

Authors
Bukhari, Syed Sabir HussainLipo, Thomas A.Kwon, Byung-il
Issue Date
Mar-2017
Publisher
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
Keywords
Current regulator; inrush current elimination; multiple load transformers; online UPS systems; voltage regulator
Citation
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, v.53, no.2, pp.1149 - 1156
Indexed
SCIE
SCOPUS
Journal Title
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS
Volume
53
Number
2
Start Page
1149
End Page
1156
URI
https://scholarworks.bwise.kr/erica/handle/2021.sw.erica/10130
DOI
10.1109/TIA.2016.2622229
ISSN
0093-9994
Abstract
Numerous industrial facilities involve the installation of load transformers with their respective loads. As these loads are engaged and disengaged, their transformers are also energized and de-energized, respectively. An inrush current, which typically occurs when a transformer is energized, can easily be observed for an online uninterruptible power supply (UPS) system feeding such loads. This paper proposes an online UPS system that eliminates the inrush current phenomenon caused by the switching-in of the load transformers. The UPS inverter specifically utilizes a fast acting current control scheme which enables it to regulate the load current during all energizing conditions of the load transformer connected to the UPS system. Experimental results are provided to validate the effectiveness of the proposed UPS system.
Files in This Item
Go to Link
Appears in
Collections
COLLEGE OF ENGINEERING SCIENCES > SCHOOL OF ELECTRICAL ENGINEERING > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Altmetrics

Total Views & Downloads

BROWSE