액체건조제(LiCl)를 이용한 멤브레인 기반 제습시스템의 성능 해석
DC Field | Value | Language |
---|---|---|
dc.contributor.author | 전우진 | - |
dc.contributor.author | 김우승 | - |
dc.contributor.author | 김영득 | - |
dc.date.accessioned | 2021-06-22T15:43:39Z | - |
dc.date.available | 2021-06-22T15:43:39Z | - |
dc.date.issued | 2016-12 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/erica/handle/2021.sw.erica/12141 | - |
dc.description.abstract | This paper presents a rigorous framework for the numerical modeling of dehumidification modules utilizing a liquid desiccant (LiCl) and flat-sheet hydrophobic polyvinylidene fluoride (PVDF) membrane. In the present work, we have extensively examined the influence of module design parameters, i.e., channel heights of both humid air and solution streams in the range of 1−5 mm and flow configurations such as parallel-, counter- and cross-flow, on the module performance in terms of heat and moisture transfers (i.e., sensible and latent effectivenesses). It is found that the sensible effectiveness increases by 15% and 22%, respectively, whilst the latent effectiveness increases by 1.9% and 3.1%, respectively, by varying the flow configuration from parallel- to cross- and counter-flow at both channel heights of 2 mm. With a change in both channel heights ranging from 1 to 5 mm, the sensible and latent effectivenesses are found to be in the range of 0.47−0.96 and 0.50−0.76, respectively, regardless of the flow configuration. | - |
dc.format.extent | 6 | - |
dc.language | 한국어 | - |
dc.language.iso | KOR | - |
dc.publisher | 대한기계학회 | - |
dc.title | 액체건조제(LiCl)를 이용한 멤브레인 기반 제습시스템의 성능 해석 | - |
dc.title.alternative | Performance investigation of membrane-based dehumidification system using a liquid desiccant (LiCl) | - |
dc.type | Article | - |
dc.publisher.location | 대한민국 | - |
dc.identifier.bibliographicCitation | 대한기계학회 2016년도 학술대회, pp 296 - 301 | - |
dc.citation.title | 대한기계학회 2016년도 학술대회 | - |
dc.citation.startPage | 296 | - |
dc.citation.endPage | 301 | - |
dc.description.isOpenAccess | N | - |
dc.description.journalRegisteredClass | other | - |
dc.subject.keywordPlus | javascript:fn_save() | - |
dc.subject.keywordAuthor | Dehumidification | - |
dc.subject.keywordAuthor | 제습 | - |
dc.subject.keywordAuthor | PVDF Membrane | - |
dc.subject.keywordAuthor | PVDF 막 | - |
dc.subject.keywordAuthor | Lithium Chloride | - |
dc.subject.keywordAuthor | 염화리튬 | - |
dc.subject.keywordAuthor | Effectiveness | - |
dc.subject.keywordAuthor | 효과 | - |
dc.identifier.url | https://www.dbpia.co.kr/journal/articleDetail?nodeId=NODE07104360 | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
55 Hanyangdeahak-ro, Sangnok-gu, Ansan, Gyeonggi-do, 15588, Korea+82-31-400-4269 sweetbrain@hanyang.ac.kr
COPYRIGHT © 2021 HANYANG UNIVERSITY. ALL RIGHTS RESERVED.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.