Experimental Verification of an Inrush Current Elimination Technique for Line-Interactive UPS SystemsLine-interactive UPS 시스템에 대한 돌입 전류 제거 기법의 실험적 검증
- Other Titles
- Line-interactive UPS 시스템에 대한 돌입 전류 제거 기법의 실험적 검증
- Authors
- 권병일
- Issue Date
- Oct-2014
- Publisher
- 대한전기학회
- Citation
- 2014년도 대한전기학회 전기기기 및 에너지변환시스템부문회 춘계학술대회 논문집, pp.1 - 3
- Journal Title
- 2014년도 대한전기학회 전기기기 및 에너지변환시스템부문회 춘계학술대회 논문집
- Start Page
- 1
- End Page
- 3
- URI
- https://scholarworks.bwise.kr/erica/handle/2021.sw.erica/21577
- Abstract
- Numerous critical loads of commercial, industrial and domestic use rely on the uninterruptible power supply system to uphold the power during voltage sags and outages and maintain the normal operation. In case of power failure or any disturbance, a UPS system generally takes over load within 1-5 msec in order to supply continuous power to load and avoid any interruption. This transition of load can cause significant inrush current phenomenon on the load transformer due to its magnetic saturation. The generation of inrush current can cause the reduction of line voltage and sometimes triggering the over current protection of a UPS system. An inrush current elimination technique was proposed before for a line-interactive UPS system. This paper actually validates the proposed inrush current elimination technique by performing experiment.