Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

다중부하 변압기의 파워링 이중변환 온라인 UPS 시스템의 과도 특성Transient Behaviour of Double-Conversion On-Line UPS Systems Powering Multiple Load Transformers

Other Titles
Transient Behaviour of Double-Conversion On-Line UPS Systems Powering Multiple Load Transformers
Authors
권병일
Issue Date
Apr-2014
Publisher
대한전기학회
Citation
2014년도 대한전기학회 전기기기 및 에너지변환시스템부문회 춘계학술대회 논문집, pp.290 - 292
Journal Title
2014년도 대한전기학회 전기기기 및 에너지변환시스템부문회 춘계학술대회 논문집
Start Page
290
End Page
292
URI
https://scholarworks.bwise.kr/erica/handle/2021.sw.erica/23296
Abstract
Numerous industrial facilities involve the installation of load transformers with their respective loads. As these loads are engaged or dis-engaged, their transformers are also connected and dis-connected. A transient current which typically occurs when the transformer is switched-in, can easily be observed for double-conversion on-line UPS systems feeding such load transformers. This paper investigates the transient behaviour of conventional double-conversion on-line UPS systems and proposes a current control strategy to eliminate the possibility of any transient inrush current during switching-in of multiple load transformers. The current control scheme is validated by the simulation results. MATLAB is used to obtain simulation results.
Files in This Item
There are no files associated with this item.