냉방시스템의 운전조건에 따른 에너지 소비특성 연구
DC Field | Value | Language |
---|---|---|
dc.contributor.author | 박기태 | - |
dc.contributor.author | 안병천 | - |
dc.date.available | 2020-03-03T11:47:37Z | - |
dc.date.created | 2020-02-24 | - |
dc.date.issued | 2019-12 | - |
dc.identifier.issn | 1738-6985 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/gachon/handle/2020.sw.gachon/19350 | - |
dc.description.abstract | The operational conditions such as cooling tower water pump flow rate, cooling tower fan flow rate, and chiller capacity in heat source equipment, and supply air temperature and chilled water temperature in air conditioner are considered to study the effects on energy consumption for central cooling system by using TRNSYS program. As a result, the optimal values of supply air temperature and chilled water temperature for minimal total energy consumption are 12℃ and 8℃. And if maximum values of cooling tower water pump and fan flow rate is decreased from 100% to 40%, energy consumptions are increased 170MJ/day and 63.2MJ/day, respectively. | - |
dc.language | 한국어 | - |
dc.language.iso | ko | - |
dc.publisher | 한국지열에너지학회 | - |
dc.relation.isPartOf | 한국지열에너지학회논문집 | - |
dc.title | 냉방시스템의 운전조건에 따른 에너지 소비특성 연구 | - |
dc.title.alternative | The Characteristics of Energy Consumption with Operational Conditions for the Central Cooling System | - |
dc.type | Article | - |
dc.type.rims | ART | - |
dc.description.journalClass | 2 | - |
dc.identifier.bibliographicCitation | 한국지열에너지학회논문집, v.15, no.4, pp.39 - 45 | - |
dc.identifier.kciid | ART002529078 | - |
dc.description.isOpenAccess | N | - |
dc.citation.endPage | 45 | - |
dc.citation.startPage | 39 | - |
dc.citation.title | 한국지열에너지학회논문집 | - |
dc.citation.volume | 15 | - |
dc.citation.number | 4 | - |
dc.contributor.affiliatedAuthor | 안병천 | - |
dc.subject.keywordAuthor | Central cooling system(중앙냉방시스템) | - |
dc.subject.keywordAuthor | Chiller capacity(냉동기 용량) | - |
dc.subject.keywordAuthor | Cooling tower fan(냉각탑 팬) | - |
dc.subject.keywordAuthor | Cooling tower water pump(냉각탑 펌프) | - |
dc.description.journalRegisteredClass | kci | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
1342, Seongnam-daero, Sujeong-gu, Seongnam-si, Gyeonggi-do, Republic of Korea(13120)031-750-5114
COPYRIGHT 2020 Gachon University All Rights Reserved.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.