냉방시스템의 운전조건에 따른 에너지 소비특성 연구The Characteristics of Energy Consumption with Operational Conditions for the Central Cooling System
- Other Titles
- The Characteristics of Energy Consumption with Operational Conditions for the Central Cooling System
- Authors
- 박기태; 안병천
- Issue Date
- Dec-2019
- Publisher
- 한국지열에너지학회
- Keywords
- Central cooling system(중앙냉방시스템); Chiller capacity(냉동기 용량); Cooling tower fan(냉각탑 팬); Cooling tower water pump(냉각탑 펌프)
- Citation
- 한국지열에너지학회논문집, v.15, no.4, pp.39 - 45
- Journal Title
- 한국지열에너지학회논문집
- Volume
- 15
- Number
- 4
- Start Page
- 39
- End Page
- 45
- URI
- https://scholarworks.bwise.kr/gachon/handle/2020.sw.gachon/19350
- ISSN
- 1738-6985
- Abstract
- The operational conditions such as cooling tower water pump flow rate, cooling tower fan flow rate, and chiller capacity in heat source equipment, and supply air temperature and chilled water temperature in air conditioner are considered to study the effects on energy consumption for central cooling system by using TRNSYS program. As a result, the optimal values of supply air temperature and chilled water temperature for minimal total energy consumption are 12℃ and 8℃. And if maximum values of cooling tower water pump and fan flow rate is decreased from 100% to 40%, energy consumptions are increased 170MJ/day and 63.2MJ/day, respectively.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - 공과대학 > 기계공학과 > 1. Journal Articles
![qrcode](https://api.qrserver.com/v1/create-qr-code/?size=55x55&data=https://scholarworks.bwise.kr/gachon/handle/2020.sw.gachon/19350)
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.