Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

국가지정 음압격리 입원치료병상의 슬라이딩 도어의 개폐속도 및 의료진의 이동속도에 따른 오염공기 유출에 관한 해석적 연구A Numerical Study on Contaminated Air Outflows according to Sliding Door Closing & Opening Speed and Medical workers’ Moving Speed of National Negative Pressure Isolation Units

Other Titles
A Numerical Study on Contaminated Air Outflows according to Sliding Door Closing & Opening Speed and Medical workers’ Moving Speed of National Negative Pressure Isolation Units
Authors
이두루나홍진관
Issue Date
2018
Publisher
대한설비공학회
Keywords
National inpatient isolation units(국가지정 입원치료 격리병상); Secondary infection(2차 감염); Air change rate(환기횟수); Differential pressure(실간차압); Opening & closing speed(개폐속도); Contaminated air(오염공기); Standard Operating Procedure(표준조작절차)
Citation
설비공학 논문집, v.30, no.5, pp.211 - 221
Journal Title
설비공학 논문집
Volume
30
Number
5
Start Page
211
End Page
221
URI
https://scholarworks.bwise.kr/gachon/handle/2020.sw.gachon/5029
DOI
10.6110/KJACR.2018.30.5.211
ISSN
1229-6422
Abstract
To prevent secondary infections in national inpatient isolation units, this study conducted flow analysis for opening/closing speeds of sliding doors of negative pressure isolation rooms and medical workers’ moving speeds among various factors that might cause outflow of contaminated air from negative pressure isolation rooms to the outside. Subject situations were divided into cases where medical workers’ moving speed remained the same while opening/closing speed of doors changed and cases where opening/closing speed of doors changed while medical workers’ moving speed remained the same to figure out internal flow characteristics of negative pressure isolation rooms and anteroom. Three speeds were designated for each of sliding door opening/closing speeds and medical workers’ moving speeds. Results showed that the outflow of contaminated air decreased as sliding door opening/closing speeds increased and as medical workers’ moving speeds decreased. Results of this study can be used as evidentiary material to set standard operation procedures to minimize diffusion of contaminated air where national inpatient isolation units are designed and operated.
Files in This Item
There are no files associated with this item.
Appears in
Collections
공과대학 > 설비·소방공학과 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Hong, Jin Kwan photo

Hong, Jin Kwan
Engineering (Department of Building Equipment System&Fire Protection Engineering)
Read more

Altmetrics

Total Views & Downloads

BROWSE