Sterilization effectiveness of in-duct ultraviolet germicidal irradiation system in liquid desiccant and indirect/direct evaporative cooling-assisted 100% outdoor air system

Authors
Bang, Jong-IlPark, Joon-YoungJo, Ye-LimJeong, Jae-WeonChoi, AnseopSung, Minki
Issue Date
Dec-2020
Publisher
PERGAMON-ELSEVIER SCIENCE LTD
Keywords
Liquid desiccant and indirect/direct evaporative cooling-assisted 100% Outdoor air system (LD-IDECOAS); In-duct ultraviolet germicidal irradiation (ID-UVGI); Irradiation analysis; Microbial contamination; Indoor air quality
Citation
BUILDING AND ENVIRONMENT, v.186, pp.1 - 11
Indexed
SCIE
SCOPUS
Journal Title
BUILDING AND ENVIRONMENT
Volume
186
Start Page
1
End Page
11
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/144228
DOI
10.1016/j.buildenv.2020.107350
ISSN
0360-1323
Abstract
Microorganism contamination in air conditioning systems can cause respiratory diseases in building occupants. This study aims to evaluate and predict the performance of an in-duct ultraviolet germicidal irradiation (IDUVGI) system to reduce the microorganisms that can grow in the liquid desiccant and indirect/direct evaporative cooling-assisted 100% outdoor air system (LD-IDECOAS). Bacteria and mold on the direct evaporative cooling (DEC) element and in the outdoor and supply air were monitored using a swab and Petrifilm for surfaces and impact sampler for air during the operation of the LD-IDECOAS. Microbial contamination was first verified in the air before performing the sterilization experiment. The experimental results showed that the airborne bacteria were reduced by 78.3% after the operation of the ID-UVGI system but there was almost no reduction in the airborne mold. The bacteria and mold concentration on the DEC surface were decreased by 99.7% and 96.7% respectively 3 h after the ID-UVGI operation. Even after the ID-UVGI system was operated for 6 days, the microbial contamination in the downstream water was not decreased significantly; the inside of the DEC element was suspected to be improperly sterilized. The operating times of the ID-UVGI system needed to inactivate the microorganisms were predicted from the UV-C intensity distribution by irradiation analysis. Legionella sp. and Penicillium sp. were predicted to be inactivated by 99.9% with UV-C exposures of 6 s and 15 min 57 s or less respectively when the LD-IDECOAS is operated at the highest air flow rate.
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE