Energy benefit of organic Rankine cycle in high-rise apartment building served by centralized liquid desiccant and evaporative cooling-assisted ventilation system

Authors
Dong, Hye-WonKim, Beom-JunYoon, Soo-YeolJeong, Jae-Weon
Issue Date
Sep-2020
Publisher
ELSEVIER
Keywords
Organic Rankine cycle; Liquid desiccant; Centralized ventilation; Decentralized ventilation; Residential building
Citation
SUSTAINABLE CITIES AND SOCIETY, v.60, pp.1 - 14
Indexed
SCIE
SCOPUS
Journal Title
SUSTAINABLE CITIES AND SOCIETY
Volume
60
Start Page
1
End Page
14
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/145161
DOI
10.1016/j.scs.2020.102280
ISSN
2210-6707
Abstract
Building heating, ventilating, and air-conditioning systems have high impacts on the energy and environmental performance of residential buildings. To reduce the energy consumption of the building for sustainable buildings and cities, this research proposed the organic Rankine cycle (ORC) applied to a centralized liquid desiccant (LD) and evaporative cooling-assisted ventilation system serving an apartment building and evaluated the energy impact of the proposed system via detailed energy simulations. As a small combined heat and power application in residential buildings, the ORC produces heat and power that are consumed by the proposed system and the building. A conventional decentralized energy recovery ventilator powered by the existing power grid was selected as a reference system. The combination of the ORC, LD, and evaporative cooling-assisted ventilation system allows decoupling of the sensible and latent cooling and offers energy benefits by reclaiming heat from the ORC compared with the reference system owing to the parallel system of energy consumption. Energy simulations were conducted for one floor of a 30-story apartment building. The proposed system exhibited 28% annual primary energy savings and provided a 54% higher annual average coefficient of performance compared with the reference system, although the proposed system consumed more fan and pump energy. The majority of the operating energy savings of the proposed system were achieved by reclaiming the waste heat from the ORC condenser.
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE