히트펌프 기반 공기 난방 시스템과 바닥 난방 시스템의 에너지 소비 비교Comparison of Energy Consumption of an Air Source Heat Pump Heating System and a Radiant Floor Heating System in an apartment building
- Other Titles
- Comparison of Energy Consumption of an Air Source Heat Pump Heating System and a Radiant Floor Heating System in an apartment building
- Authors
- 황유진; 정재원
- Issue Date
- Nov-2019
- Publisher
- 한국생태환경건축학회
- Keywords
- 히트펌프; 공기난방; 바닥난방; 환기; Heat Pump; Air Heating; Radiant Floor Heating
- Citation
- 한국생태환경건축학회 2019년도 추계국제학술발표대회 논문집, v.19, no.2, pp.138 - 139
- Indexed
- OTHER
- Journal Title
- 한국생태환경건축학회 2019년도 추계국제학술발표대회 논문집
- Volume
- 19
- Number
- 2
- Start Page
- 138
- End Page
- 139
- URI
- https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/146769
- ISSN
- 1975-3616
- Abstract
- The purpose of this study is to analyze and compare the energy performance of an air heating system with a heat pump and a radiant floor heating system with an energy recovery ventilator in an apartment building. The thermal load in a conditioned zone was derived with the simulation tool TRNSYS 18 and the total energy consumption of the system was calculated from Engineering Equation Solver (EES) using each component model. The COP of the heat pump was calculated as 3.16. The results show that the proposed system reduces 21.8% energy consumption compared with a conventional floor heating system.